Permit Number: T03BU01216
Parcel: 136091980

Review Status: Completed

Review Details: GRADING

Permit Number - T03BU01216
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/03/2003 PAUL MACHADO ENGINEERING REVIEW Denied To: TJ Bednar & Co.
4846 N. Davis Avenue
Tucson, Arizona 85705

SUBJECT: 1341 S. Placita Brisa Serena
Grading Plan T03BU01216 (First submittal)
T14S, R15E, Section 24

RESUBMITTAL REQUIRED: Grading Plan

The Grading Plan (GP) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Grading Plan:

1. Please include a response letter to the comments along with the corrected copies with resubmittal.
2. A plot plan will be required when the type of model has been determined.
3. Remove "Site Plan" from title.
4. Add note: "Depress all landscaped areas a maximum of 6" for water harvesting"
5. Call out the names of all washes.
6. Call out all slopes and stabilization material (concrete, riprap, gabbions or vegetation).
7. Slopes of 3H: 1V, hand placed riprap is suggested.
8. Slopes of 2H: 1V or greater grouted riprap is suggested.
9. List percentage of the graded area.
10. Flow arrows within the site to show drainage scheme.
11. Show proposed swale on the plans.

If you have any questions, I can be reached at 791-5550, or pmachad2@ci.tucson.az.us
Paul Machado
Senior Engineering Associate
06/05/2003 LOREN MAKUS NPDES REVIEW Passed
06/09/2003 PATRICIA GEHLEN ZONING REVIEW Denied Zoning
6/09/2003
Zoning may not review and approved grading plans until Engineering has approved the grading plans
06/10/2003 PATRICIA GILBERT NPPO REVIEW Denied An approved site plan is required prior to grading plan approval. Please submit an approved copy of the site plan. Remove "site" from the title.

Clearly label on the plan all the natural undisturbed set aside areas. Add a general note stating that these areas will be protected with temporary fencing prior to the start of grading/construction. A pre-permit inspection will be required prior to grading plan aprroval to verify the fencing is in place.

All saguaros are required to be preserved in place or transplanted on site. Please clearly delineate on the grading plan the location of the saguaros on site and state on the plan if they will be transplanted or preserved in place.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/12/2003 CINDY AGUILAR OUT TO CUSTOMER Completed
06/10/2003 ANGIE SHOFFSTALL REJECT SHELF Completed