Permit Number: T03BU01215
Parcel: 136092060

Review Status: Completed

Review Details: GRADING

Permit Number - T03BU01215
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/03/2003 LOREN MAKUS ENGINEERING REVIEW Denied TO: TJ Bednar & Co. DATE: June 3, 2003
4846 N. Davis Avenue FROM: Loren Makus
Tucson, Arizona 85705 Engineering Division

SUBJECT: 1270 S. Placita Brisa Serena
Grading Plan T03BU01229 (First Submittal)
T14S, R15E, Section 24


RESUBMITTAL REQUIRED: Grading Plan

The Grading Plan (GP) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Grading Plan

1. Please include a response letter explaining how each comment was addressed along with the resubmittal of the corrected copies of the grading plan.
2. Add note: "Depress all landscaped areas a maximum of 6" for water harvesting"
3. Call out all slopes and stabilization material (concrete, riprap, gabions, or vegetation).
4. The proposed graded area of this plan exceeds the 10128 square foot limit established by tentative plat and rezoning conditions. Revise the grading plan so that the graded area meets the requirement.
If you have any questions, I can be reached at 791-5550, or lmakus1@ci.tucson.az.us.
Loren Makus
Senior Engineering Associate
06/05/2003 LOREN MAKUS NPDES REVIEW Passed
06/09/2003 PATRICIA GILBERT NPPO REVIEW Denied An approved site plan is required prior to grading plan approval. Please submit an approved copy of the site plan. Remove "site" from the title.

Clearly label on the plan all the natural undisturbed set aside areas. Add a general note stating that these areas will be protected with temporary fencing prior to the start of grading/construction. A pre-permit inspection will be required prior to grading plan aprroval to verify the fencing is in place.

All saguaros are required to be preserved in place or transplanted on site. Please clearly delineate on the grading plan the location of the saguaros on site and state on the plan if they will be transplanted or preserved in place.
06/09/2003 PATRICIA GEHLEN ZONING REVIEW Denied Zoning
6/9/2003
Zoning can not review and approved grading plans until Engineering has approved them.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/12/2003 CINDY AGUILAR OUT TO CUSTOMER Completed
06/10/2003 ANGIE SHOFFSTALL REJECT SHELF Completed