Permit Number: T03BU00992
Parcel: 13824182A

Review Status: Completed

Review Details: GRADING

Permit Number - T03BU00992
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/01/2003 PATRICIA GILBERT NPPO REVIEW Passed Approved exception.
05/05/2003 LOREN MAKUS NPDES REVIEW Passed Disturbed (and site) area both under 1 acre.
05/05/2003 DOUG WILLIAMS ENGINEERING REVIEW Denied SUBJECT: Children's Medical Center SW
REVIEWER: Doug Williams
DATE: 5 May 2003
ACTIVITY NUMBER: T03BU00992

SUMMARY: Engineering Division has reviewed the Site - Grading and Utilites plan received on 1 May 2003. Approval is not recommended at this time. Please address the following comments:

GRADING PLAN COMMENTS:

1. Depict and label grading limits on sheet C2;
2. Depict roof drainage direction(s) with discharge locations noted. Please include reference to splash pads or other energy dissipating type items at downspout locations;
3. Provide a typical pavement section;
4. Address drainage patterns on the east perimeter of the site. It appears that existing patterns along this portion of the site discharge to the east. Overall existing drainage patterns should be maintained as closely as possible under developed conditions;
5. Proposed finished grades appear to be directing site runoff toward the northwest corner of the parking lot/maneuvering area (low point at 71.25). Existing patterns appear to be draining as sheet flow along the north lot line. Please revise as necessary;
6. The benchmark elevation provided does not match the elevation provided on Sheet T-1; please revise necessary.
Please address all of the above comments. Resubmittal shall include a revised Sheet C2 - Site Plan - utilities and grading.
If you have any questions, I can be reached at 791-5550, extension 1189 or Dwillia1@ci.tucson.az.us.

Douglas Williams
Sr. Engineering Associate
Engineering Division
Development Services Department
05/06/2003 PATRICIA GEHLEN ZONING REVIEW Denied Zoning
5/6/2003
Zoning may not review and approve grading plans until Engineering/Floodplain has approved the plans

Final Status

Task End Date Reviewer's Name Type of Review Description
05/20/2003 TAMI ACHONG OUT TO CUSTOMER Completed