Permit Number: T03BU00987
Parcel: 134030240

Review Status: Completed

Review Details: GRADING

Permit Number - T03BU00987
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/15/2003 PAUL MACHADO ENGINEERING REVIEW Denied To: Bill Belobraydic
Resident/Owner 9250 E. Old Spanish Trail
Tucson, Arizona 85710
SUBJECT: 9250 E. Old Spanish Trail
Grading Plan T03BU00987 (First submittal)
T14S, R15E, Section 15

RESUBMITTAL REQUIRED: Grading Plan

The Grading Plan (GP) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Grading Plan:

1. Grading plan clearly marked "GRADING PLAN".
2. Please include a response letter to the comments along with the corrected copies with the resubmittal.
3. Add note: "Depress all landscaped areas a maximum of 6" for water harvesting"
4. List administrative address/site address on plans.
5. Provide a Location Map (3" = 1 mile)
6. Use Engineering Scale only.
7. List all Cut and Fill quantities in cubic yards. If both are 0 cy, please list.
8. Please show the proposed roof drainage patterns, 100% of the 10-year flow must be conveyed under the sidewalks. Please provide supporting calculations to demonstrate compliance with D.S. 3-01.4.4. If the location(s) of the roof scuppers have not yet been decided, add a general note indicating sidewalk scuppers (per COT/SD) will be used when the roof scuppers locations have been designed.
9. Call out all slopes and stabilization material (concrete, riprap, gabbions or vegetation).
10. Slopes of 3H: 1V require hand placed riprap.
11. Cut or fill slopes require a 2' minimum setback from property line.
12. Drainage patterns with percent slopes (Show patterns within the first 100 feet from the property line).
13. Flow arrows, grades and flow rates within and adjacent to site to show drainage scheme.
14. A Stormwater pollution prevention plan is required. Contact Paul P. Machado at 791-5550 x1193 for additional information.
15. Show proposed and existing contour lines on same sheet. An overlay is will not work for record keeping purposes.
16. Please show dimensioned right-of-way, including any applicable Major Streets and Routes (MS&R) Plan right-of-way per D.S. 2-02.2.1.19.


If you have any questions, I can be reached at 791-5550 x1193, or pmachad2@ci.tucson.az.us
Paul Machado
Senior Engineering Associate
05/19/2003 ANY NPDES REVIEW Denied
05/21/2003 JOE LINVILLE NPPO REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
05/27/2003 MONICA VALDEZ OUT TO CUSTOMER Completed
05/21/2003 ANGIE SHOFFSTALL REJECT SHELF Completed