Permit Number - T03BU00873
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/01/2003 PATRICIA GILBERT NPPO REVIEW Passed
05/08/2003 LOREN MAKUS NPDES REVIEW Denied A stormwater pollution prevention plan is required for all construction activities this project site and for all of the lots covered by the drainage report. Information on the SWPPP requirements can be obtained from ADEQ at http://www.adeq.state.az.us/environ/water/permits/stormwater.html
05/08/2003 LOREN MAKUS ENGINEERING REVIEW Denied DATE: May 8, 2003
To: Carlos Korvig
Proprietor
518 W. Kennington
Tucson, Arizona 85746

FROM: Loren Makus
Engineering Division


SUBJECT: 946 W Teton
Grading Plan T02BU00873 (First submittal)
T15S, R13E, Section 14

RESUBMITTAL REQUIRED: Grading Plan and Drainage Report

The Grading Plan (GP) cannot be approved as submitted. The Drainage Report was reviewed for purposes of grading of this lot only. Please address the following review comments prior to the next submittal.

Grading Plan:

The following items must be revised or added to the Grading Plan. Please include a letter with the next submittal addressing how the comments have been addressed.

1. Include the name of the person who prepared the plan. IBC Chapter 36 Section 9.7
2. Use Engineering Scale only.
3. Indicate basis of elevation based on City of Tucson Datum. DS 2-02.2.1.A.23
4. Show the grading limits. Grading limits must reflect the fill that was placed on this site prior to the submmittal of this grading permit application. IBC Chapter 36 Section 9.7.2
5. Revise the plan to show the exact location of the retaining wall. Label with a reference to the building permit number for the wall.
6. Show proposed drainage patterns and sufficient finish grades to substantiate the drainage. Include enough detail of adjacent properties to show that drainage patterns described in the drainage report will be maintained. DS 2-02.2.1.A.16
7. Revise the plan to include the detail of the drainage swale along Teton Street as shown in the drainage report . IBC Chapter 36 Section 9.4
8. Provide the basin maintenance responsibility per DS 2.3.1.6 C 1 and 2. Discuss the status of basin construction as described in the drainage report.
9. Provide perc test results as referenced on page 7 of the drainage report.
10. Show and label the 100-year flood peak discharges entering and exiting the site.
11. Prepare and submit a Stormwater Pollution Prevention Plan for all construction activities on this lot and the other lots described in the drainage report.

If you have any questions, I can be reached at 791-5550, or lmakus1@ci.tucson.az.us
Loren Makus
Senior Engineering Associate
05/12/2003 PATRICIA GEHLEN ZONING REVIEW Denied Zoning
5/12/2003
Grading plans may not be reviewed and approved until Engineering/Floodplain is approved.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/12/2004 TAMI ACHONG OUT TO CUSTOMER Completed
05/12/2003 ANGIE SHOFFSTALL REJECT SHELF Completed