Review Date Reviewer's Name Type of Review Description Status Comments
09/05/2003 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Denied 1. Changes made to architectural plans are required to be done by the architect of record. Registrant to make changes.
2. Calculations and plans to be designed to the 2000 IBC. Revise plans and calculations.
3. Wind design to be a minimum of 90 mph 3 sec. Gust. Revise plans