Permit Number: T03BU00727
Parcel: Unknown

Address:
3333 N WALNUT AV

Review Status: Completed

Review Details: GRADING

Permit Number - T03BU00727
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/28/2003 LOREN MAKUS NPDES REVIEW Denied Walnut Property
3333 North Walnut Avenue
T03BU00727

Reviewed by Loren Makus

Construction of Rillito Crossing Drive must be addressed in a SWPPP. The SWPPP presented indicates that Rillito Crossing Drive will have been paved. All work on Rillito Crossing Drive that occurs west of Christopher City Wash must be addressed in this or another SWPPP. Provide evidence of such coverage or include in this SWPPP.

Identify the operator(s) with operational control over day to day activities. (Part IV.C.1) Where an operator is unknown (such as a yet to be determined general contractor) leave space for the identity to be supplied later. Each operator must also submit an NOI to ADEQ and to the City of Tucson.

General location map showing receiving waters within 1 mile (Part IV.C.2.e) Include Christopher City Wash and Walnut Wash in the general location map.

In the narrative identify the name of nearest receiving waters that will receive discharges from disturbed areas of the project including Christopher City Wash and Walnut Wash. (Part IV.C.4)

Specify that concrete, stucco and drywall washout will not be discharged to drainage ways or paved streets. (Part IV.D.7)

For control measures, identify the implementation sequence and the operator responsible, (Part IV.D.1) and why BMPs were selected. (Part IV.D.2.b)

Describe interim and permanent stabilization practices, including an implementation schedule. (Part IV.D.4.a) Indicate the scheduling for installation of rip rap in Walnut Wash and Christopher City Wash in order to minimize erosion during the construction process. Also show where revegetation is to occur and specify a schedule.

Provide for recording dates when major grading activities occur. (Part IV.D.4.c.i)

Provide for recording dates when construction temporarily or permanently ceases on a portion of the site. (Part IV.D.4.c.ii)

Provide for recording dates when stabilization measures are initiated and completed. (Part IV.D.4.c.iii)

For drainage areas of 10 or more acres, provide temporary or permanent sediment basin with storage for calculated volume of runoff from a 2 year, 24 hour storm. (Part IV.D.5.a.i) Provide information showing the total drainage areas for each outfall location. Show how sediment traps meet the requirement of this section of the general permit.

For drainage areas less than 10 acres, smaller sediment basins and/or sediment traps shall be used. (Part IV.D.5.a.iii)

On Plan Sheets or Site Map show areas of soil disturbance and areas which will not be disturbed, (Part IV.C.3.b)

On Plan Sheets or Site Map show locations where stabilization practices are planned. (Part IV.C.3.d) Include areas of revegetation.

Specify the inspection schedule: either once per week, OR once per 14 days and within 24 hours of a 0.5” rainfall. (Part IV.H.1)

Inspection can be reduced to monthly if, site has been temporarily stabilized, OR Construction is in an arid area, AND construction is occurring during the seasonal arid period. A monthly schedule must also include pre and post storm inspections. (Part IV.H.2)
04/14/2003 LAITH ALSHAMI ENGINEERING REVIEW Denied Laith Alshami, Engineering Comments, 04/14/2003

1- Provide the project administrative address.
2- Complete the Grading Plan Case # (T02BUXXXX).
3- Lots 1, 2, 9, 22 and 23 do not comply with the differential grading requirements. In order for the Grading Plan to be approved with the proposed non-compliant grades, the Developer/Consultant must satisfy the requirements stated in Section 13-Fills of Chapter 36 Excavation and Grading (Local Amendments of the International Building Code). Please see the excerpt of Section 13 which deals with this issue:

"Placement of fill in excess of two (2) feet [or a finished floor elevation (FFE) in excess of two (2) feet plus the slab thickness] above existing grade at any location in the outer one hundred (100) feet of the developing site (less any intervening non-developable property outside of the site) shall require:

a) Written justification based on engineering/technical reasons.
b) Written permission of the Director of the Development Services Center (DSC) or his/her assignee.
c) Notification of the property owner(s) adjacent to the fill site (with copies to the Council Office and the Director of DSC) prior to the approval of a grading plan. Said notification shall include reference to this ordinance, the justification presented as the basis for the excess fill, the approval letter from DSC, and the name, address, & phone number of the owner/developer and the engineer of record. This notification shall occur early in the development process.
d) Preparation of a mitigation plan (i.e. additional setbacks, terracing, enhanced buffering/landscaping, etc.) acceptable to a simple majority of the notified property owners. The acceptability of the mitigation plan by the notified property owner(s) must be documented and made a part of the approved grading plan and permit. If the owner/developer and the notified property owner(s) cannot reach consensus on a mitigation plan within 15 working days of receipt of the mitigation plan by the notified property owners, the Director of DSC shall review the issues and information and then render a final decision."

Please be advised that the Tentative Plat was approved with the condition that the differential grading requirements must be met on the Grading Plan.
4- Provide the parcel dimensions and bearings.
5- Dimension the Common Areas and all lots.

Laith ALshami, Floodplain Comments, 04/14/2003

1- Show and label the 100-year floodplain and erosion hazard setbacks.
2- Provide details that show the dimensions of the proposed the erosion control riprap pads downstream of the proposed sidewalk scuppers.
3- In detail E/3, the riprap note should point to the riprap shown on the slope. Additionally, describe and dimension the 12' riprap downstream of the slope.
04/14/2003 PATRICIA GEHLEN ZONING REVIEW Denied Zoning
4/16/2003
Grading plans may not be reviewed or approved until Engineering/Floodplain has approved them
04/18/2003 PATRICIA GILBERT NPPO REVIEW Denied Submit an approved copy of the Tentative plat and the Native Plant Preservation Plan.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/21/2003 MONICA VALDEZ OUT TO CUSTOMER Completed
04/18/2003 MONICA VALDEZ REJECT SHELF Completed