Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: 3RD PARTY REVIEW-COMMERCIAL
Permit Number - T03BU00717
Review Name: 3RD PARTY REVIEW-COMMERCIAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/08/2003 | EROSE1 | FIRE | REVIEW | Needs Review | |
| 05/08/2003 | GP | 3RD PARTY REVIEW-COMMERCIAL | REVIEW | Denied | STRUCTURAL COMMENTS Sheet 1 of 2 1. Please address the wall thickness on plan details for the two freestanding and retaining elements. Complete calculations on page 4 to show development of wall reinforcement as moment appears to be larger than moment used for 5' simple retaining wall; the wind pressure shall be included. Also recheck sliding resistance requirements. 2. Clarify and address on plan transverse reinforcement in wall foundation. 3. Provide note on plan regarding masonry compressive strength requirement. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/08/2003 | ELAINE ROSE | OUT TO CUSTOMER | Completed |