Permit Number: T03BU00717
Parcel: Unknown

Address:
2500 E RIVER RD

Review Status: Completed

Review Details: 3RD PARTY REVIEW-COMMERCIAL

Permit Number - T03BU00717
Review Name: 3RD PARTY REVIEW-COMMERCIAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/08/2003 EROSE1 FIRE REVIEW Needs Review
05/08/2003 GP 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied STRUCTURAL COMMENTS
Sheet 1 of 2
1. Please address the wall thickness on plan details for the two freestanding and retaining elements. Complete calculations on page 4 to show development of wall reinforcement as moment appears to be larger than moment used for 5' simple retaining wall; the wind pressure shall be included. Also recheck sliding resistance requirements.

2. Clarify and address on plan transverse reinforcement in wall foundation.

3. Provide note on plan regarding masonry compressive strength requirement.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/08/2003 ELAINE ROSE OUT TO CUSTOMER Completed