Permit Number: T03BU00529
Parcel: 13612004K

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T03BU00529
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/27/2003 Paul Machado ENGINEERING REVIEW Denied To: Miguel Urcadez
Arquitectura 375 S. Meyer Ave.
Tucson, Arizona 85701

SUBJECT: 9640 E. Golf Links Road
Grading plan T03BU00529 (First Review)
T14S, R15E, Section 26

RESUBMITTAL REQUIRED: Grading Plan and Drainage Report

The Grading Plan (GP) and Drainage Report (DR) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Grading Plan:

1. Grading plan clearly marked "GRADING PLAN".
2. Please include a response letter to the comments along with the corrected copies with re-submittal.
3. Please address the swale adjacent to the building and any adverse impact it may have on the building.
4. Drainage study addendum is not allowed. The information should be incorporated into the Drainage study.
5. Two sets of the grading plan are required for review. The "site grading plan" is not allowed as the grading plan.

Drainage report:

1. A $150.00 drainage study review fee is required along with the next submittal.
2. Please address the swale adjacent to the building and any adverse impact it may have on the building.
3. Drainage study addendum is not allowed. The information should be incorporated into the Drainage study.

If you have any questions, I can be reached at 791-5550 x1193, or pmachad2@ci.tucson.az.us
Paul Machado
Senior Engineering Associate
06/27/2003 PATRICIA GILBERT NPPO REVIEW Approved NPPO exception per JL on 3/18/03.
07/03/2003 ANY NPDES REVIEW Passed
07/08/2003 PETER MCLAUGHLIN ZONING REVIEW Denied Zoning
7/8/2003
Grading may not be reviewed and approved until engineering has approved the plans.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/09/2003 LISA LESNY OUT TO CUSTOMER Completed
07/09/2003 LISA LESNY REJECT SHELF Completed
07/09/2003 LISA LESNY APPROVAL SHELF Completed