05/09/2003 DOUG WILLIAMS ENGINEERING REVIEW Denied SUBJECT: El Rio OB/GYN Associates
REVIEWER: Doug Williams
DATE: 9 May 2003
ACTIVITY NUMBERS: T03CM00019 and T03BU00024

SUMMARY: Engineering Section has reviewed the grading plan received on May 2, 2003. Approval is not recommended at this time. The following comments are offered:

1. It appears that approximately the western half of the site runoff may drain directly north, as proposed on the plan, exiting the site via the driveway entrance without being directed into the retention/detention basin (see area north of proposed spot elevation 75.2). Please demonstrate that site drainage will be directed into the basin, in order to achieve the retention volume approved in the drainage report;

2. The top of basin elevation labeled on the plan indicates that the 100-year retention/detention volume will not be contained in the basin as currently proposed. Revise north top of basin elevations and the retention basin section elevations as necessary, to clearly demonstrate containment of the 100-year volume, corresponding with a water surface elevation of 74.9;

3. Provide a note, or indicate on the plan, water harvesting maximization in all landscape areas.

Provide a revised Grading Plan addressing the above comments. If you have any questions, I can be reached at 791-5550, extension 1189.

Douglas Williams
Senior Engineering Associate
Engineering Section
Development Services
05/20/2003 PATRICIA GEHLEN ZONING REVIEW Denied Zoning
5/20/2003
Zoning may not review and approve grading plans until Enigneering has approved