09/25/2002 PAUL MACHADO FLOODPLAIN REVIEW Denied To: Lawrence and Anita Hunt
4721 E. Paseo Del Bac
Tucson, Az. 85718


SUBJECT: 3232 N. Christmas Ave.,
Floodplain use permit T02OT01438 (FirstReview)
T13S, R14E, Section 29


RESUBMITTAL REQUIRED: Floodplain use permit


The Floodplain use permit (FUP) cannot be approved at this time. Please address the following review comments prior to the next submittal.


Floodplain Use Permit:


1. The proposed amount of the combined additions ($40,000) exceeds 50% of the value of the house alone ($37,649). If this amount cannot be adjusted (redesigned), then the entire residence (existing and proposed) must be raised to 1 foot above the base flood elevation.
2. Show the calculations on sheet 1 (list source), i.e.: Price of existing house alone = $75,298/ 2 = $37,649
Proposal by Licensed contractor (list source) = $37,000
This shall include a note stating that the percentage is under 50%.
3. Show existing Sight Visibility Triangles on site plan. Revise per redlines.

If you have any questions, I can be reached at 791-5550 or pmachad2@ci.tucson.az.us
Paul Machado,
Senior Engineering Associate,

Final Status

Task End Date Reviewer's Name Type of Review Description
10/01/2002 TAMI ACHONG OUT TO CUSTOMER Completed