Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: FLOODPLAIN
Permit Number - T02OT01358
Review Name: FLOODPLAIN
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/26/2002 | MATT FLICK | FLOODPLAIN | REVIEW | Approv-Cond | September 26, 2002 (Special Inspection Required). FLOODPLAIN USE PERMIT NO. T02OT01358. ADDRESS: 2508 East River Road PROPERTY OWNER'S NAME: Hacienda Del Sol Partners LLC The applicant is authorized to use a portion of the flood hazard area in the City of Tucson on the property described as (legal description): Irr Pcl in SE4 of Section 20, T-13-S, R-14-E for the purpose of constructing apartment buildings, office, and other items as shown on the approved development plan for "The Villas at Hacienda Del Sol", D01-0038. The applicant agrees to comply with City of Tucson Floodplain and Erosion Hazard, and Watercourse Amenities, Safety and Habitat regulations, and are particularly bound by the conditions stated below. Violation of any of the conditions stated or referred to below, as determined by the City Engineer, shall be grounds for revocation of this permit. Responsibility for renewal of this permit, if necessary, is with the applicant. Issuance of this permit does not constitute a waiver of other requirements contained in the Tucson City Code, Land Use Code, or any other Federal, State, or local regulation. No use other than as permitted herein is allowed. Additional uses allowed under City of Tucson Floodplain and Erosion Hazard Regulations and Watercourse Amenities, Safety, and Habitat regulations require the issuance of an additional Floodplain Use Permit. The following conditions shall apply to this permit. (Or refer to Chapter 26 page 35) 1. All work shall conform to the attached plans (Drainage Report/Statement) which are made part of this permit. 2. The existing drainage patterns at the property lines shall not be obstructed. 3. Within 5 (five) days of issuance of this permit, through completion of the project, notification must be posted and maintained in a conspicuous place on the job site stating "Construction proceeding under requirements of City of Tucson Floodplain Use Permit No. T02OT01358. For information please call 791-5550." 4. Except as approved by the City Engineer prior to the start of construction, development under this permit shall not obstruct, retard or divert the existing flow of floodwaters from or to adjacent properties. 5. This permit becomes invalid and is subject to additional floodplain review, if any required development permit (s') changes the configuration of the structure and or site development. 6. Buildings #11, #12, #14, #15, and #21are currently shown to be within the floodplain of the Rillito River per FIRM Panel 040076-04019C-1645K dated February 8, 1999. The final Certificate of Occupancy is not to be issued until the Development Services Department Engineering Division receives one or more of the following: A. A revised FIRM showing the buildings to be out of the 100-year flood hazard area. B. A Letter of Map Revision showing the buildings to be out of the 100-year flood hazard area. C. Properly-completed elevation certificates showing the minimum finished floor of the buildings to be at least one foot (1') above the adjacent 100-year water surface elevation in the Rillito River. 7. Development to conform to the approved development plan (D01-0038) and grading plan (T02BU02014) for this development. This Floodplain Use Permit will be automatically revoked and becomes invalid if conditions set forth in this permit are not complied with. Also, this permit will expire one year from its date of issue. Renewal of this permit will require a new application, review and approval of that application by the City of Tucson, Development Services Department, Engineering Section. (EXPIRATION DATE) Month: 09 Day: 26 Year: 2003 Note the final inspection or certificate of occupancy will be on hold until the Elevation Certificate is completed and returned to our office. APPLICANT NAME: Hacienda Del Sol Partners LLC ADDRESS: PO Box 31364 PHONE NO.: (520) 349-8282 _____________________________ APPLICANT'S SIGNATURE DATE The applicant is authorized by the City Engineer to receive a floodplain use permit subject to the above referenced conditions and restrictions. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/07/2002 | TAMI ACHONG | OUT TO CUSTOMER | Completed |