Review Status: Completed
Review Details: FLOODPLAIN
Permit Number - T02OT01262
Review Name: FLOODPLAIN
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/23/2002 | JIM TATE | FLOODPLAIN | REVIEW | Denied | Flood Use Permit is denied. The drainage structure from Det 9 encroaches into the floodplain. It is not apparant on the Grading Plan the nature of the bank protection (in the wash) for this drainage structure. The exact nature of the encroachement (the drainage structure) must be shown. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/01/2002 | TAMI ACHONG | OUT TO CUSTOMER | Completed |