Permit Review Detail
Review Status: Completed
Review Details: FLOODPLAIN
Permit Number - T02OT01212
Review Name: FLOODPLAIN
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/22/2002 | JIM TATE | FLOODPLAIN | REVIEW | Denied | Flood Use Permit is denied. 1. On page 6 of the Drainage Report the Floodplain and Erosion Hazard Ordinance cited is a Pima County ordinance. This project is in the City of Tucson. The erosion hazard setback must be calculated using the method found in the Standards Manual for Drainage Design and Floodplain Management, SMDDFM, 7.6. For lessor setbacks the banks must be stabilized. See Tucson Code Chapter 26 Section 26-7.2 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/25/2002 | LISA LESNY | OUT TO CUSTOMER | Completed |