Permit Number: T02OT01211
Parcel: 140441760

Review Status: Completed

Review Details: FLOODPLAIN

Permit Number - T02OT01211
Review Name: FLOODPLAIN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/15/2002 JIM TATE FLOODPLAIN REVIEW Denied Flood Use Permit is denied.
Section 26-6.2 of the Tucson Code:
"All new and replacement water supply and sanitary sewage systems shall be designed to minimize or eliminate infiltration of floodwaters into the system and discharge from systems into floodwater. On-site waste disposal systems shall be located to avoid impairment to them or contamination from them during flooding."
The approved Tentative Plat shows all of the on-site sewage disposal system on Lot 85 as outside the floodplain. The Site Plan submitted with the Flood Use Permit has located part of the proposed system in the floodplain.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/15/2002 MONICA VALDEZ OUT TO CUSTOMER Completed