Review Date Reviewer's Name Type of Review Description Status Comments
08/02/2002 JIM EGAN FIRE REVIEW Denied MINIMUM ONE-HOUR FIRE RATED WALL REQUIRED BETWEEN COVERED PARKING STRUCTURE AND WEST/NORTH PROPERTY LINES.
08/06/2002 PETER MCLAUGHLIN HANDICAP-SITE REVIEW Denied See zoning comments.
08/06/2002 PETER MCLAUGHLIN ZONING REVIEW Denied SITE PLAN TRANSMITTAL

TO: David Williams
1421 W. Chapala Drive
Tucson, AZ 85704

FROM: Peter McLaughlin
Senior Planner

FOR: Patricia Gehlen
Principal Planner

PROJECT:
Sierra Tile
4155 E. Speedway Blvd.
Parking Plan/Site Plan

TRANSMITTAL: August 6, 2002

COMMENTS: Please attach a response letter with the next submittal, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.


1. Per letters from the City Zoning Administrator, the parking lot to the north of the building (on parcel III - zoned R-2) is considered legal non-conforming based on the site plan approved on July 8, 1977. However, as stated in the letter dated December 20, 2001, a new site plan must be submitted for review and approval for the commercial storage use on the parcel located across the street to the east at 1124 N. Bryant Ave. Please provide a copy of approved site plan for 1124 N. Bryant Ave.

2. Revise parking calculations to be based solely on the principal use of retail tile sales, which may be parked at a ratio of one (1) vehicle space per 400 square feet of floor area. Therefore, if the gross floor area is 20,460 square feet as stated in general note 6, the required parking is 51 vehicle spaces (20,460 square feet รท 400 square feet = 51 parking spaces).
LUC 3.3.4

3. Show the zoning boundary between the C-2 and R-2 zoned properties. Revise the zoning of the property to the west of parcel III to read "R-2".

4. With 52 parking spaces provided, 3 handicapped accessible parking spaces are required per IBC Tale 1106.1 and access aisles and access ramps must be provided in accordance with American National Standard Chapters 4 & 5. Please revise site plan drawing.
IBC
ANSI

If you have any questions about this transmittal, please call Peter McLaughlin, (520) 791-5608.
08/08/2002 JOE LINVILLE NPPO REVIEW Approved Exception, previously developed site.
08/08/2002 JOE LINVILLE LANDSCAPE REVIEW Approved
08/20/2002 ANY FLOODPLAIN REVIEW Denied See engineering folder.
08/20/2002 PAUL MACHADO ENGINEERING REVIEW Denied To: The WLB Group
Ed Roll, P.E.


SUBJECT: 4155 E. Speedway Blvd.
Site plan T02CM01113 (First Review)
T14S, R14E, Section 03


RESUBMITTAL REQUIRED: Site Plan


The Site Plan (SP) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Site Plan:

1. Please provide Drainage patterns (flow arrows) and finished grades per D.S. 2-02.2.1.16.
2. Add note to plans "Depress all landscaped areas 6" max. for water harvesting".
3. Where is the refuse dumpster located? Please show per D.S. 6-01.0
4. Show existing and future (if applicable) sight visibility triangles per D.S. 2-02.2.1.10.
5. A private improvement agreement may be necessary for work performed within the Right-of-way. Contact Department of transportation at (520) 791-4249 for information.
6. A DSMR is required for any construction in the future sight visibility triangle.
7. It is not clear whether the north parking area is already paved. Please address.



If you have any questions, I can be reached at 791-5550 or pmachad2@ci.tucson.az.us
Paul Machado
Senior Engineering Associate