Review Details: FLOODPLAIN

Permit Number - T02OT00751
Review Name: FLOODPLAIN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/23/2002 JIM TATE FLOODPLAIN REVIEW Denied A Flood Use Permit is denied.

Tucson Code Sec. 26-4.3
"any alteration, addition or repair to a nonconforming building or structure which would result in increasing its flood damage potential by fifty (50) percent or more shall be elevated to or above the regulatory flood elevation."

1. The construction estimate for the remodel and addition included "by owner" cost estimates. The estimate must be performed by a contractor and include appropriate labor and material costs.

2. All additions to the structure since August 3, 1984 must be documented. The total cumulative value of all such additions and proposed additions determine the increase in flood damage potential of the structure.

3. The supplied Appraisal Report indicates the existing depreciated value of the building is $80,163. A maximum value of all additions and proposed additions without elevating any structure is $40,081. The proposed improvements exceed this amount and do not include any previous improvements.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/28/2002 TAMI ACHONG OUT TO CUSTOMER Completed