01/10/2003 REYES ARVAYO BUILDING-RESIDENTIAL REVIEW Denied GENERAL REQUIREMENTS FOR GRUOP CARE FACILTIES
T02OT00511 ------SECOND REVIEW----01-10-03
FLOOR PLANS:

DRAWING ARE INCOMPLETE NEED INFORMATION COMPLYING WITH R-4 REQUIREMENTS

1 SHOW LOCATIONS OF SMOKE DETECTORS PER R317. NOTE THAT ALL SMOKE DETECTORS MUST BE
INTERCONNECTED WITH A POWER SOURCE FROM THE BUILDING WIRING, AND SHALL BE EQUIPPED WITH
BATTERY BACKUP.

4. ADDITIONAL EXIT ILLUMINATION REQUIRED -ON EXIT TRAVEL

5. INDICATE WIDTH OF HALLWAYS

6. INDICATE NUMBER OF CLIENTS IN EA BEDROOM.

7. SHOW RAMPS ON DRAWINGS - 1 IN 12 AND 36" WIDE

8. SHOW GRAB BARS ON DRAWINGS