Permit Number: T02OT00277
Parcel: 14021011A

Address:
1105 E DREXEL RD

Review Status: Completed

Review Details: SITE

Permit Number - T02OT00277
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/15/2002 JIM EGAN FIRE REVIEW Approved
05/24/2002 DAVID RIVERA ZONING REVIEW Denied TO: McCarty Engineering FROM: David Rivera
320 W. Alturas Senior Planner
Tucson, AZ 85705
(520) 770-1318 FOR: Patricia Gehlen
Principal Planner

PROJECT: T02OT00277
1105 E. Drexel Road
Sunny Side Headstart School
Site Plan Review (1st review)
TRANSMITTAL: May 24, 2002

COMMENTS: Please attach a response letter with the next submittal, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.
CODE SECTION/
DEVELOPMENT
STANDARD

1. Please provide a copy of the recorded lot of the combo covenant. Add as a general note, "Lot Combo per Lot Combo Covenant DKT _____ PAGE ______." (Previous Comment: A lot combo covenant is required in addition to the tax code parcel combo, which appears to have been completed. The lot combo covenant must be recorded and a copy of the recorded document must be provided with the next submittal package for review. For your convenience, I have attached a copy of the required document to the application. These comments have been placed in permits plus. If you like to have the lot combo document emailed to you please call me or email me with the request. This will certainly cut down on the process time for you and us. Permits cannot be issued until such time as the covenant has been recorded and provided to the Development Services Department - Zoning Review Section.
DS 2-02.2.1.A.5

2. As of this review date the dedication of Drexel Road had not been completed. Per Jim Stoyanoff, of the COT Real Estate Division, the paperwork was in process. The dedication must be accepted by COT prior to final approval of the site plan. (Previous Comment: The dedication of land for the Drexel right-of-way must be completed prior to approval of the site plan. The docket and page numbers for the dedication must be listed. The Lot Combo covenant must also be recorded and the docket and age numbers listed on the plan.

3. For Zoning purposes, the site plan may be stamped and approved over the counter when the remaining comments have been addressed. Please see David Rivera.

If you have any questions about this transmittal, please call David Rivera, (520) 791-5608.

C:\planning\DSC\T01OT00277b.doc
05/31/2002 PHIL SEADER HANDICAP-SITE REVIEW Approved
06/06/2002 JIM TATE ENGINEERING REVIEW Denied Dedication of right-of-way along Drexel Road must be complete prior to site plan approval.
06/06/2002 JAMES TATE FLOODPLAIN REVIEW Approved
06/10/2002 JOE LINVILLE LANDSCAPE REVIEW Approved
06/10/2002 JOE LINVILLE NPPO REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/28/2002 TAMI ACHONG OUT TO CUSTOMER Completed