Permit Number: T02OT00277
Parcel: 14021011A

Address:
1105 E DREXEL RD

Review Status: Completed

Review Details: SITE

Permit Number - T02OT00277
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/25/2002 JIM EGAN FIRE REVIEW Denied 1. SUBMIT COMPLETE CODE REVIEW CHECKLIST.
2. FIRE HYDRANT REQUIRED. INDICATE LOCATION OF NEW/EXISTING FIRE HYDRANT(S) ON PLAN.
03/08/2002 JIM TATE FLOODPLAIN REVIEW Denied See engineering.
03/08/2002 JIM TATE ENGINEERING REVIEW Denied The following items must be revised or added to the Site Plan. Please include a response letter with the next submittal that states how all engineering and flood plain comments have been addressed.

Site Plan
1. Show and dimension the future MS&R right-of-way for Drexel (100'). (DS 2-02.2.1.A.19)

2. Dimension to the future curb (11 ft. from the future r.o.w. to the face of curb).
(DS 2-02.2.1.A.21)

3. Show the future sight visibility triangles. (DS 2-02.2.1.A.10)

4. The site plan shows a water surface elevation of 35.4. The drainage report outflow hydrograph shows 34.9. The top of bank is 34.5. Please correct. If the basin is meant to overflow the bank (ie not contained within the outflow structure) please discuss in the drainage report.

Drainage Report
1. Please discuss offsite flows in more detail. How do flows from the industrial park to the east effect the property? What are peak flows on Drexel and Leghorn? What is the potential flooding from offsite flows? (Standards Manual for Drainage Design and Floodplain Management, 2.3.1.3.2)
03/08/2002 JIM TATE SANITATION REVIEW Approved
04/01/2002 DAVID RIVERA ZONING REVIEW Denied TO: McCarty Engineering
320 W. Alturas
Tucson, AZ 85705
(520) 770-1318

FROM: David Rivera
Senior Planner

FOR: Patricia Gehlen
Principal Planner

PROJECT: T02OT00277
1105 E. Drexel Road
Sunny Side Headstart School
Site Plan Review (1st review)
TRANSMITTAL: April 01, 2002

COMMENTS: Please attach a response letter with the next submittal, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. A lot combo covenant is required in addition to the tax code parcel combo form, which appears to have been completed. The lot combo covenant must be recorded and a copy of the recorded document must be provided with the next submittal package for review. For your convenience, I have attached a copy of the required document to the application. If you would like to have the lot combo document emailed to you please call me or email me with the request. This will certainly cut down on the process time for you and us. Permits cannot be issued until such time as the covenant has been recorded and provided to the Development Services Department - Zoning Review Section.
DS 2-02.2.1.A.5

2. Not Used

3. Please indicate the Leghorn Avenue future curb location. Leghorn is not a major street but at sometime in the future a cur and sidewalk will constructed. The building setback from Leghorn Avenue must be based on the greatest of 21 feet or the height of the structure from the nearest edge of travel lane. I realize that at this time there is no existing curb or sidewalk and the street building setback has been properly shown. Please contact the Engineering Section to assist in determining the future curb location for a local street.
DS 2-02.2.1.A.7

4. Please add a fully dimensioned detail drawing for the bicycle parking facilities that demonstrates compliance with D.S. 2-09. The facility is not visible from the street and therefore the cyclist must be directed to the facility by directional signage. Please add the directional signage to the plan and annotate.
DS 2-02.2.1.A.9

5. At least one sidewalk will be provided from each street on which a project has frontage. A sidewalk must be provided from the Leghorn Avenue area to the project. See D.S. 2-08.4.1
DS 2-02.2.1.A.12

6. If applicable, indicate the locations of existing or proposed freestanding signage or existing billboards. The location, type and size must be annotated.
DS 2-02.2.1.A.13

7. If applicable, indicate graphically existing or proposed freestanding lighting. The type of lighting and pole heights must be annotated.
DS 2-02.2.1.A.25

8. Add a wheel stop barrier to the six (6) parking spaces adjacent to the landscape border along the northwest corner of the site. The barrier is shown on the landscape plan but was not added to the site plan. See landscape review comments regarding landscape borders, screening, and NPPO requirements.
DS 2-02.2.1.A.27

9. Under general note one (1) add the existing use. If vacant state so.
DS 2-02.2.1.A.31

10. Indicate graphically or by notes in all other instances how all of the special exception conditions have been met. The dedication of land for the Drexel right-of-way must be completed prior to approval of the site plan. The docket and page numbers for the dedication must be listed. The Lot Combo covenant must also be recorded and the docket and age numbers listed on the plan.

If you have any questions about this transmittal, please call David Rivera, (520) 791-5608.
04/02/2002 JOE LINVILLE NPPO REVIEW Denied Revise the "fencing standards" and "plant protection during development" notes on Sheet L1.0 to refer to Development Services rather than the Parks and Recreation Department. The standard has been revised to reflect changes in development review. DS 2-15.6.0, LUC 3.8.6.6

Revise L1.0 note 27 to refer to the City of Tucson and revise the color coding and flaaging notes to cite the appropriate Tucson Code.
04/02/2002 JOE LINVILLE LANDSCAPE REVIEW Denied The Loading zone must be screened with a min. 6' high masonry wall from the property to the north. LUC Table 3.7.2-I
Depict and identify the required wall on the site and the landscape plans.

A five foot high masonry screen wall is required between the
parking lot/vehicular use area and all adjacent properties. Revise the site and landscape plans for consistency, showing the required walls, revising keynotes and desriptions as necessary. Remove references to chain link fencing where appropriate. LUC Table 3.7.2-I

A five foot high screen is required along the development side of the Leghorn street landscape border. Revise the landscape plan to provide the required continuous screen. LUC Table 3.7.2-I, SE 01--41.

The site plans indicate that the access road from Leghorn Avenue is for playground service. Per Special Exception condition the road is limited to fire access use only. The fire lane access gate is to be the same height and must be designed to complement the adjacent screening. Provide details of the access gates and screening. SE 01-41
04/03/2002 PHIL SEADER HANDICAP-SITE REVIEW Denied

Final Status

Task End Date Reviewer's Name Type of Review Description
04/04/2002 DELMA ROBEY OUT TO CUSTOMER Completed