Permit Number: T02OT00046
Parcel: 10604191A

Address:
426 E MOHAVE RD

Review Status: Completed

Review Details: SITE

Permit Number - T02OT00046
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/28/2002 JIM EGAN FIRE REVIEW Approved
02/06/2002 DAN CASTRO ZONING REVIEW Denied COMMENTS: Please attach a response letter with the next submittal, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.
CODE SECTION/ DEVELOPMENT STANDARD

1. The number of vehicle parking spaces required may not be verified for compliance until the number of bedrooms for each unit, including the existing residence is noted on the site plan. Since this site has changed from single family residence to multi-family residential LUC 3.3.4 required that all units be parked based on the number of bedrooms in each unit.
D.S. 2-02.2.A.8/ D.S. 2-02.2.2.A.4/ L.U.C. 3.3.4

2. a) The number of bicycle parking spaces required may not be verified until the number of vehicle parking spaces required is clarified. See above comment number one (1).
b) Note the type of bicycle parking spaces required and provided under the calculations block on sheet one (1).
D.S. 2-02.2.1.A.9/ D.S. 2-02.2.2.A.4/ L.U.C. 3.3.4

3. Revise the proposed use noted under general note number one (1) on sheet one (1) to "Multi-family Residential."
D.S. 2-02.2.1.A.31

4. All requested changes must be made to the site and landscape plans
D.S. 2-07.2.1.A
02/11/2002 JOE LINVILLE NPPO REVIEW Denied Native Plant Preservation Plan or application for exception to LUC 3.8 required.
02/11/2002 JOE LINVILLE LANDSCAPE REVIEW Denied 1. All areas of the site, if disturbed must be treated with an appropriate dust control material . This requirement applies to all areas of the site. Please include the provision for decomposed granite, or equal, for all disturbed undeveloped areas of the site. LUC 3.7.2.7
2. Portions of the vehicular use area located within 100 feet the adjacent street must be screened. Revise the plans to provide a 5' high screen between the landscape border and
the vehicular use area. LUC Table 3.7.2-I
3. A minimum 10' landscape border as well as a 5' screen may be required in the location of the ingress/egress for the existing residence.
4. Screen walls may not obscure the visibility of the street landscape border from the street. Screen walls may not encroach more than the width of the wall into the street landscape border. LUC Secs. 3.7.3.2.B and C. Revise the plans to provide the required 10' landscape border and screening located as required by the LUC. Show and label the screen walls consistently on the site and landscape plans.
5. The proposed land use (multi-family) must provide a 10' interior landscape border, when located adjacent to a residentially zoned property. Per LUC 3.7.3.2.C.3.d an exception to this requirement is allowed, only if the adjacent use is similar. In this case the exception only applies where multi family development is adjacent. Please identify all adjacent uses (single family or multifamily) in order to qualify for the exception and revise the plans to provide the interior borders where appropriate.
6. The vehicular use area (see specific uses) on the site must screened with a minimum 5' high masonry wall when located within 100 feet of adjacent residentially zoned properties. Revise the plans to provide the required screen walls. LUC Table 3.7.2-I
7. The landscape plan may require additional revision in order to meet Native Plant Preservation requirements
05/01/2002 MATT FLICK FLOODPLAIN REVIEW Denied FLOODPLAIN:

1. A Floodplain Use Permit is required ($50 application fee + $150 for engineering report review)

2. Channel grades shown on site plan indicate flow going uphill. Revise channel grades.

3. Indicate location of any perimeter walls to be constructed.

4. It is highly recommended that the floodplain use permit application and grading permit application be concurrent.
05/01/2002 MATT FLICK ENGINEERING REVIEW Denied ENGINEERING:

1. A grading plan is required. It is highly recommended that
the grading plan application and floodplain permit
application be concurrent. More detailed information will be
necessary on the grading plan than is shown on the site
plan.

2. Indicate PC/COT Standard Detail nomenclature for
driveways, sidewalks.

3. The benchmark is given as NAVD88. The elevation of
the units is given as NGVD29. Provide an equation and
state which is used for the grade elevations.

4. A Right-of-Way Use Permit is necessary for the work
within Mohave Road right-of-way. Contact the Permits
& Codes Section of TDOT at 791-5100 for more info.
05/01/2002 MATT FLICK SANITATION REVIEW Approved SANITATION:

Add a note stating that the trash enclosure will be constructed in accordance with Development Standard 6-01.
05/01/2002 PHIL SEADER HANDICAP-SITE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/04/2002 DELMA ROBEY OUT TO CUSTOMER Completed