Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T02EL01883
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/14/2002 | RANDY SCHULER | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1) It is unclear how many separate buildings there are. Provide a site plan that clearly depicts the footprint and perimeter walls of each building. 2) Panel M1 appears to be in a different building than panel A therefore circuits A-20ab, 22ab, 24ab (6 circuits from panel A) cannot be served from panel M1. See 99NEC 225 part B. 3) Momentary Amp Probe readings to ascertain loads is not a NEC approved method. See 99NEC 220-35 for approved methodology. 4) Panel schedule M1 indicates circuits 25 through 35 as existing. It does not appear panel M1 served panel A (the panel the above circuits were removed from). Please clarify. 5) It appears panel 4 is in a different building than the receptacle circuits in room 20. See 99NEC 225 part B. |