Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T02EL01882
Parcel: 10603148A

Address:
125 W YAVAPAI RD

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T02EL01882
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/11/2002 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Denied 1) It is unclear how many separate buildings there are. Provide a site plan that clearly depicts the footprint and perimeter walls of each building.
2) It appears circuits EW2-18,20,22,24,26 are served from a panel located in a separate building. See 99NEC 225 part B and comply.
3) Clarify where panel LP is located.
4) If panel AS is in a different building than the switchboard serving it, provide a grounding electrode system for panel AS. See 99NEC 250-32
5) Momentary Amp Probe readings to ascertain loads is not a NEC approved method. See 99NEC 220-35 for approved methodology.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/17/2002 TAMI ACHONG OUT TO CUSTOMER Completed