Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T02EL01882
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/11/2002 | RANDY SCHULER | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1) It is unclear how many separate buildings there are. Provide a site plan that clearly depicts the footprint and perimeter walls of each building. 2) It appears circuits EW2-18,20,22,24,26 are served from a panel located in a separate building. See 99NEC 225 part B and comply. 3) Clarify where panel LP is located. 4) If panel AS is in a different building than the switchboard serving it, provide a grounding electrode system for panel AS. See 99NEC 250-32 5) Momentary Amp Probe readings to ascertain loads is not a NEC approved method. See 99NEC 220-35 for approved methodology. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/17/2002 | TAMI ACHONG | OUT TO CUSTOMER | Completed |