Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T02EL00732
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/22/2002 | RANDY SCHULER | ELECTRICAL-COMMERCIAL | REVIEW | Denied | E-1 1) Provide seal off fittings on the downstream side of all conduits penetrating the wall of the lift station. It appears if junction boxes are used they should be on the interior of the lift station as all conduits penetrate the wall of the lift station underground. See 99 NEC 501-5(b)(2) 2) See page 4 of 4 on the Civil drawing. Please note the Civil drawing appears to combine the power and the control conductors in the same conduit and does not contain any seals. Unless an acceptable exception derived from the 99NEC can be sited the drawing will have to be revised to comply with the 99NEC in every respect. 3) The SO cords cannot penetrate the lift station wall. See 99NEC 400-8(2) |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/04/2002 | TAMI ACHONG | OUT TO CUSTOMER | Completed |