Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T02EL00732
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/17/2002 | RANDY SCHULER | ELECTRICAL-COMMERCIAL | REVIEW | Denied | E-1 1) Provide seal off fittings on the downstream side of all conduits penetrating the wall of the lift station. It appears if junction boxes are used they should be on the interior of the lift station as all conduits penetrate the wall of the lift station underground. 2) Show all control conduits with appropriate seal off fittings on the plan. E-2 1) All exterior fixtures must have an efficacy rating of 45 lumens per watt or greater. 2) Keynote number 4 should read TS not ATS as the transfer switch is manual. E-3 1) The TS is incorrectly connected. 2) It appears what you are describing is actually a phase converter not an inverter. Please correct all reference to the inverter throughout the entire plan. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/22/2002 | LISA LESNY | OUT TO CUSTOMER | Completed |