Review Date Reviewer's Name Type of Review Description Status Comments
04/17/2002 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Denied E-1
1) Provide seal off fittings on the downstream side of all conduits penetrating the wall of the lift station. It appears if junction boxes are used they should be on the interior of the lift station as all conduits penetrate the wall of the lift station underground.
2) Show all control conduits with appropriate seal off fittings on the plan.
E-2
1) All exterior fixtures must have an efficacy rating of 45 lumens per watt or greater.
2) Keynote number 4 should read TS not ATS as the transfer switch is manual.
E-3
1) The TS is incorrectly connected.
2) It appears what you are describing is actually a phase converter not an inverter. Please correct all reference to the inverter throughout the entire plan.