Review Date Reviewer's Name Type of Review Description Status Comments
03/14/2002 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Denied E-1
1) Provide the fuse size for the secondary conductors of the 1MVA transformer.
E-3
1) Clarify the interlock sequence for the SES. It appears at least 2 sections are served from one utility transformer.
2) Clarify where keynote 1 is utilized.
General Comments
1) Provide specifications and descriptions for the manhole(s).
2) Provide transformer specifications.
3) Revise specification 16111-5 E 1 paragraph "c" to include junction boxes. See 99NEC 370-55(e) and 370-72(e).
03/14/2002 DOUG WILLIAMS ENGINEERING REVIEW Passed Right of Way excavation permit required - contact Permits and Codes - Eng. Div. Transportation Dept.