Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/14/2002 | RANDY SCHULER | ELECTRICAL-COMMERCIAL | REVIEW | Denied | E-1 1) Provide the fuse size for the secondary conductors of the 1MVA transformer. E-3 1) Clarify the interlock sequence for the SES. It appears at least 2 sections are served from one utility transformer. 2) Clarify where keynote 1 is utilized. General Comments 1) Provide specifications and descriptions for the manhole(s). 2) Provide transformer specifications. 3) Revise specification 16111-5 E 1 paragraph "c" to include junction boxes. See 99NEC 370-55(e) and 370-72(e). |
03/14/2002 | DOUG WILLIAMS | ENGINEERING | REVIEW | Passed | Right of Way excavation permit required - contact Permits and Codes - Eng. Div. Transportation Dept. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
03/25/2002 | TAMI ACHONG | OUT TO CUSTOMER | Completed |