Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T02CM05974
Parcel: 115044130

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/FLOOD

Permit Number - T02CM05974
Review Name: RESIDENTIAL BLDG/ZONING/FLOOD
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/08/2003 PETER MCLAUGHLIN ZONING REVIEW Approved
01/08/2003 DOUG WILLIAMS FLOODPLAIN REVIEW Approved
01/08/2003 PETER MCLAUGHLIN NPPO REVIEW Passed
02/04/2003 DAVE WITT BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T02CM05974

2/4/03 1144 N. 1ST AVE.

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:

1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ¼ INCH = 1-FOOT SHALL BE USED
FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE.

2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.


FOUNDATION PLANS:

1. FOOTING WIDTHS FOR ONE-STORY, PER TABLE R403.1:

- 16" MINIMUM; WOOD FRAME

2. PROVIDE LANDINGS IN ACCORD WITH R312

3. DETAILS 1&2 ON 2 , AN 8" ANCHOR BOLT DOESN'T APPEAR TO PROVIDE 7" EMBED.


FLOOR PLANS:

1. LABEL ALL ROOMS AND SPACES.

2. IS THE WINDOW OVER THE BATH TUB SAFETY GLAZED ?

3. NOTE THAT BATHTUB ENCLOSURE SHALL BE FINISHED WITH TO A HEIGHT OF 72" ABOVE THE FLOOR PER R307.2

4. HOW DOES THE LOFT….STOREAGE LOFT……..APPLY TO R316……..?

STRUCTURAL PLANS:

1. SPECIFY LUMBER GRADE FOR THE WCHF.

2. DETAIL 2 ON 3 , THE RIDGE BOARD IS REQUIRED TO COVER THE ENTIRE PLUMB CUT OF THE RAFTER. SEE R802.3




PLUMBING PLANS:

1. THE UNIT COUNT IN THE PLUMBING FIXTURE SCHEDULE SHOULD BE IN ACCORD WITH THE STATE PLUMBING CODE ( THE '94 U.P.C. WITH STATE AMMENDMENTS ).

ELECTRICAL PLANS:

1. IS THE RECEPTACLE IN THE BATH TUB SPACE IN CONFLICT WITH E3902.10 ?

2. PLEASE SIZE THE FEEDERS AND GROUNDS TO THE SUB-PANELS.




IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
DAVE WITT @ 791-5550 EXT. 110


NOTE: AS OF 2-02-01 THE CITY OF TUCSON HAS ADOPTED THE 2000 IRC EXCEPT FOR THE PLUMBING PORTION WHICH IS THE STATE PLUMBING CODE.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/11/2003 MONICA VALDEZ OUT TO CUSTOMER Completed