Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T02CM05931
Parcel: 12302122A

Address:
2852 E EDISON ST

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/FLOOD/WWM

Permit Number - T02CM05931
Review Name: RESIDENTIAL BLDG/ZONING/FLOOD/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/27/2003 DAVE WITT BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T02CM05931
1/27/03
PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

GENERAL REQUIREMENTS:

1. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

2. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.

FOUNDATION PLANS:

1. DIMENSION THE WALL THICKNESS, FOOTING WIDTH THICKNESS AND DEPTH INTO UNDISTURBED SOIL FOR
EACH FOOTING TYPE AND CONDITION PER TABLE R403.1.

2. FOOTING WIDTHS FOR ONE-STORY, PER TABLE R403.1:
- 16" MINIMUM; WOOD FRAME

3. LOCATE AND DETAIL ALL FOOTINGS FOR THE FOLLOWING:
MUST HAVE CONTINUOUS FOOTING AT GARAGE OPENING FOR BRACED WALL DESIGN NOT A TURN DOWN

4. ALL FOUNDATION HOLD-DOWNS AND ANCHOR BOLT SPACING FOR SHEAR WALLS SHALL BE SPECIFIED AND
LOCATED.

FLOOR PLANS:

1. SHOW COMPLIANCE WITH R303.1 PROVIDING NATURAL LIGHT INTO ROOMS (8%).

2. SHOW COMPLIANCE WITH R303.1 PROVIDING NATURAL VENTILATION (4%).

3. SHOW COMPLIANCE WITH R310 PROVIDING EGRESS FROM BEDROOMS.----AS INDICATED DOES NOT MEET CODE
- MAXIMUM SILL HEIGHT OF 44"
- MINIMUM NET CLEAR AREA OF OPENING OF 5.7SF.
- MINIMUM NET CLEAR DIMENSIONS OF OPENING OF 24" HEIGHT BY 20" WIDTH.

4. COMPLY WITH R309.2. PROVIDE ½" GYPSUM BOARD ON ALL WALLS COMMON TO THE GARAGE AND HOUSE.
WHERE SEPARATION IS A FLOOR-CEILING ASSEMBLY, THE STRUCTURE SUPPORTING THE SEPARATION SHALL
ALSO BE PROTECTED BY A MINIMUM ½" GYPSUM BOARD OR EQUIVALENT. NOTE DOORS BETWEEN HOUSE
AND THE GARAGE SHALL BE MINIMUM 1-3/8" SOLID CORE, PER R309.1

STRUCTURAL PLANS:

1. SPECIFY DESIGN CRITERIA ON PLANS. VALUES FOR FLOOR DEAD LOAD AND LIVE LOAD, ROOF DEAD LOAD
AND LIVE LOAD.

2. COMPLETELY DETAIL ALL CONNECTIONS AND CROSS-REFERENCE TO THE FOUNDATION AND FRAMING
PLANS:
- HOLD DOWN LOCATIONS AND TYPE

3. PROVIDE BRACING DETAILS AND NOTES FOR EXTERIOR FRAME WALLS AND MAIN CROSS-STUD PARTITIONS,
OR USE FULLY BRACED, PER R602.10.3. A MINIMUM PANEL WIDTH OF 48" IS REQUIRED TO EFFECTIVELY
BRACE THE PARTITION. SEE TABLE R602.10.3, CATEGORY "C". IF BRACING DOES NOT COMPLY, PROVIDE A
LATERAL ANALYSIS OR ALTERNATE DESIGN TO BE REVIEWED BY THE PLANS EXAMINER. WIND FORCES
FOR SINGLE STORY RESIDENCES SHALL USE 90 MPH, EXPOSURE "B". TWO STORY RESIDENCES OR AREAS OF
HIGHER WIND SHALL USE EXPOSURE "C".
ELEVATIONS:

1. INDICATE ALL MATERIALS USED; STUCCO, CONCRETE BLOCK, GLASS BLOCK, ROOFING SYSTEMS, SIDING,
VENEERS, ETC.

2. SHOW CALCULATION OF ATTIC VENTILATION AREA IN COMPLIANCE WITH R806.2. NOTE LOCATION OF ALL
VENTS NEEDED TO COMPLY.

SECTIONS - DETAILS - MISC. NOTES:

1. PROVIDE A BUILDING CROSS-SECTION. MORE THAN ONE MAY BE REQUIRED TO CLEARLY ILLUSTRATE HOW
THE STRUCTURE IS BUILT.
CROSS REFERENCE ALL DETAILS FROM CROSS SECTION TO DETAIL PAGE

2. WOOD SILL PLATES SHALL BE FOUNDATION GRADE REDWOOD OR PRESSURE-TREATED WOOD PER R324.

PLUMBING PLANS:

1. WATER LINE: PROVIDE TOTAL FIXTURE DEMAND & MAXIMUM DEVELOPED LENGTH
SIZE OF WATER LINE FROM METER TO HOUSE MISSING ALSO

2. INDICATE LOCATION OF 2 WAY CLEANOUT

3. THE CITY OF TUCSON HAS NOT ADOPTED THE PLUMBING SECTION OF THE IRC 2OOO. THE CURRENT CODE BEING USED IS THE 1994 UPC WITH THE STATE AMENDMENTS. ALL PLANS MUST REFERENCE TO THIS CODE.

ELECTRICAL PLANS:

1. NOTE ON PLANS: ELECTRICAL WORK SHALL COMPLY WITH CHAPTERS 33 - 42, 2000 IRC.

MODEL ENERGY CODE:

1. PROVIDE ENERGY CALCULATIONS PER THE 1998 IECC, OR COMPLY WITH IRC CHAPTER 11.

2. CALL OUT ON THE PLANS THE "R" VALUES OF INSULATION, AS WELL AS THE "U" VALUES OF THE WINDOWS
AND DOORS IN CONFORMANCE WITH THE ENERGY CALCULATIONS PROVIDED.

IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
TERRY STEVENS @ 791-5550 EXT. 1112
01/29/2003 GERRY KOZIOL WWM REVIEW Approved
12/30/2002 MICHAEL ST. PAUL NPPO REVIEW Passed
12/30/2002 MICHAEL ST. PAUL ZONING REVIEW Approved
12/30/2002 DOUG WILLIAMS FLOODPLAIN REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/29/2003 LISA LESNY OUT TO CUSTOMER Completed