Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T02CM05880
Parcel: 13323111R

Address:
199 N PANTANO RD

Review Status: Completed

Review Details: 3RD PARTY REVIEW-REVISION/OTHER

Permit Number - T02CM05880
Review Name: 3RD PARTY REVIEW-REVISION/OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/23/2003 WILDAN 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied GENERAL COMMENTS:

1. This project has been reviewed for conformance with the 2000 IBC, 1997 UAC, 2000 IMC, 1998 IECC, 1999 NEC codes with local modifications, and the 1994 UPC with State of Arizona Amendments. Any revisions to this plan will require an additional review and approval by Willdan.

PLUMBING COMMENTS:

1. The proposed new 2-inch diameter sanitary branch line is shown serving a 6-fixture-unit 3-inch diameter trap urinal, and two 2-fixture unit floor drains for a total of 10-fixture units. A 2-inch diameter sanitary branch line shall not serve a 6-unit trap, nor shall a 2-inch diameter drain line serve more than a total of 8-fixture units. Please review and correct. Reference UPC Table 7-5.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/23/2003 ELAINE ROSE OUT TO CUSTOMER Completed