Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/23/2003 | WILDAN | 3RD PARTY REVIEW-COMMERCIAL | REVIEW | Denied | GENERAL COMMENTS: 1. This project has been reviewed for conformance with the 2000 IBC, 1997 UAC, 2000 IMC, 1998 IECC, 1999 NEC codes with local modifications, and the 1994 UPC with State of Arizona Amendments. Any revisions to this plan will require an additional review and approval by Willdan. PLUMBING COMMENTS: 1. The proposed new 2-inch diameter sanitary branch line is shown serving a 6-fixture-unit 3-inch diameter trap urinal, and two 2-fixture unit floor drains for a total of 10-fixture units. A 2-inch diameter sanitary branch line shall not serve a 6-unit trap, nor shall a 2-inch diameter drain line serve more than a total of 8-fixture units. Please review and correct. Reference UPC Table 7-5. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
07/23/2003 | ELAINE ROSE | OUT TO CUSTOMER | Completed |