Permit Number - T02CM05794
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/21/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
| 03/31/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Recalculate plumbing schedule using the values shown on Tables 7-3 and A-2, UPC. 2. Size all sections of natural gas pipe. 3. Coordinate size, slope, and connections of RWL under building with Civil (C4). 4. Coordinate size and material of SP-1 discharge with Civil (C4). |
| 03/31/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 04/15/2003 | PATRICIA GEHLEN | ZONING | REVIEW | Denied | Zoning 4/17/2003 Building plans may not be reviewed and approved until the site plan is approved. |
| 04/24/2003 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Approved |