Permit Number: T02CM05794
Parcel: 11501155D

Address:
2160 N 6TH AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T02CM05794
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/21/2003 JIM EGAN FIRE REVIEW Approved
03/31/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Recalculate plumbing schedule using the values shown on Tables 7-3 and A-2, UPC.
2. Size all sections of natural gas pipe.
3. Coordinate size, slope, and connections of RWL under building with Civil (C4).
4. Coordinate size and material of SP-1 discharge with Civil (C4).
03/31/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
04/15/2003 PATRICIA GEHLEN ZONING REVIEW Denied Zoning
4/17/2003
Building plans may not be reviewed and approved until the site plan is approved.
04/24/2003 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Approved