Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T02CM05789
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/03/2003 | Linda Buczynski | ELECTRICAL-COMMERCIAL | REVIEW | Passed | PREVIOUSLY APPROVED 7/7/03 No changes in current submittal. |
| 12/10/2003 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Denied | .. T02CM05789 .. 251 W IRVINGTON RD .. 12/10/03 ..DGL. S1. SEE PRIOR COMMENT S2. PROPERLY DETAIL FIRE-RATED METAL STUD WALL/S AND PROVIDE COPY OF THE FIRE LISTING, TO JUSTIFY THE FIRE-RATED DETAILS, ON THE DRAWINGS. S2. SEE PRIOR COMMENT S3 : 1. PROVIDE EXIT HARDWARE ON GATES, PER IBC SEC #1003.3.2, AS THE AREA OF REFUGE IS LESS THAN 50 FEET FROM THE AMPHITHEATER CANOPY. THIS HAS THE EFFECT OF REDUCING THE ALLOWABLE AREA OF THE AREA OF REFUGE BELOW THAT REQUIRED FOR THE OCCUPANT LOAD OF 305. ALSO THIS OCCUPANT LOAD OF 305 REQUIRES A MINIMUM OF TWO EXITS ( COMPLYING WITH ALL EXIT REQUIREMENTS ) FROM THE AREA OF REFUGE. REF IBC SEC 1005 AND TABLE 1005.2.1. SEE PRIOR COMMENT S3.1. 2. PROVIDE FINISHED GRADES, AS REQUESTED IN PRIOR COMMENT S 3.2. MAXIMUM ALLOWABLE SLOPE AT LANDINGS OF 1/50. 3. SEE PRIOR COMMENT S3.4. EXIT HARDWARE REQUIRED. 4. SEE PRIOR COMMENT S3.5. EXIT HARDWARE REQUIRED. 5. SEE PRIOR COMMENT S3.6. PROVIDE PROPER EXTENSION AT BOTTOM OF STAIRS, PER ANSI SEC 505.10.3. S3. SEE PRIOR COMMENT S4. SHOW ON ARCHITECTURAL DRAWINGS A0 AND A1 AND CIVIL DRAWING C2 FFE'S FOR : LEVEL LANDINGS ( MIN 5' x 5' AT EXIT GATES AND DOORS ) ; RAMP AREAS [ MAX SLOPE 1:12 W/ HANDRAILS, CROSS SLOPES, LANDINGS ( 60 INCHES MIN IN LENGTH ), REF ANSI SEC 405 ] ; CURB RAMPS ( ANSI SEC 406 W/ LEVEL LANDINGS); COORDINATE. SEE PRIOR COMMENT S4.1. Prior Comments Dated 11/5/03. Question? Call Douglas Laakso, Structural Plans Examiner, (520) 791-5550 x 1111. |