Permit Number: T02CM05789
Parcel: 13707045D

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T02CM05789
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/30/2003 Robert Sherry PLUMBING-COMMERCIAL REVIEW Denied 1. Resolve the difference between drawings C-3 and P-1.2 with regard to the location of the building water supply line.
2. Provide up and downstream manhole rim elevations, and sewer inverts. Fourth request.
3. Revision 1 (10/23/03), sheet A6 redefined the walls surrounding rooms 107, 108, and 109 as 1-hour rated fire partitions. Provide protection of the fire partition penetrations in compliance with Section 607.5.3, IMC 2000.
10/31/2003 Doug Laakso BUILDING-COMMERCIAL REVIEW Denied .. DGL .. 11/5/03 .. 4TH REVIEW .. COMMENTS #S1 THROUGH #S10. PRIOR COMMENTS DATED 10/7/03.
S1. DETAIL HOW FIRE-RATING IS ACCOMPLISHED AT FEC. SEE PRIOR COIMMENT #S5,S7 AND S11.11:
1. SOUTH WALL OF KITCHEN/STORAGE
2. EAST WALL OF KITCHEN/STORAGE.
S2. PROVIDE DETAILS AND LISTINGS, ON DRAWINGS FOR FIRE-RATED CONSTRUCTION, PER PRIOR COMMENT #S7.
S3. SEE PRIOR COMMENT #S11.
1. EXIT GATES TO MEET EXIT REQUIREMENTS, CALCULATION ON DRAWING A0, WITH OCCUPANT LOAD OF 155 ; AREA OF REFUGE MUST ACCOMMODATE ALL OCCUPANTS ~300+ , EXPLAIN/JUSTIFY. SEE PRIOR COMMENT #S11.2. 2. SEE PRIOR COMMENT #S11.4. CLARIFY HOW LANDINGS AT DOORS AND ACCESSIBILITY IS MAINTAINED AT KITCHEN/STORAGE/PLATFORM,
REF. CIVIL DWGS.,A7,A0, COORDINATE FFE.
3. SEE PRIOR COMMENT #S11.5 CLEARLY SHOW HOW EXIT DISCHARGE ( IBC SEC 1006 ) IS PROVIDED, MAINTAIN EXIT WIDTH TO THE PUBLIC WAY.
4. SEE PRIOR COMMENT #S11.6.
SEE COMMENT #S3.1 ABOVE.
5. SEE PRIOR COMMENT #S11.8.
SEE COMMENT #S3.1 ABOVE.
6. SEE PRIOR COMMENT #S11.9.
SEE ANSI A117.1-98 ed , FIG #505.10.
S4. SEE PRIOR COMMENT #S12.
1. INDICATE ENTIRE ACCESSIBILE ROUTE, DUE TO MULTIPLE FFE'S, RAMPS, LANDINGS, PARKING FACILITIES, PER IBC SECTIONS #1101 THROUGH #1108. SEE PRIOR COMMENT #S12.1.
2. SEE PRIOR COMMENT #S12.2. RAMP AT EAST ACCESSIBILE PARKING SPACE IS NOT ACCEPTABLE
IN ACCESS AISLE, CLARIFY GRADES, etc.,REF. DRAWING #C1, EXPLAIN NEED FOR LOCATION OF ACCESSIBILE PARKING SO FAR FROM BUILDINGS
AS THESE ARE REQUIRED BY SECTION 1106.5 OF THE IBC TO BE LOCATED ON " THE SHORTEST ACCESSIBILE ROUTE OF TRAVEL FROM ADJACENT PARKING TO AN ACCESSIBILE BUILDING ENTRANCE." WHY SHOULD THESE LOCATIONS BE APPROVED AS COMPLYING WITH THE CODE? S5. SEE PRIOR COMMENT #S13. PLEASE USE CODE CALCULATED OCCUPANCY LOADS PER IBC TABLE 1003.2.2.2, ( 303 @ CLASSROOM, 2 @ KITCHEN, ~ 206 @ AMPHITHEATER ) vs 145 USED.REVISE PER IBC.
S6. SEE PRIOR COMMENT #S14, #S15 AND #S16. PROVIDE RESPONSE FROM SOILS ENGINEER. CTS RESPONSE NOT ATTACHED, PLEASE PROVIDE.
S7. SEE PRIOR COMMENT #S18.
ADDRESS MANEUVERING CLEARANCES ( ANSI SEC 404), REACH RANGES ( ANSI SEC 308 ), ACCESS TO SINKS, KITCHENS ( ANSI SEC 804 ),SEATING AT TABLES, COUNTERS, AND WORK SURFACES ( ANSI SEC 902 ), SEE ANSI A117.1-98 ed.
S8. SEE PRIOR COMMENT #S20.
NO CTS LETTER ATTACHED, PLEASE PROVIDE.
S9. SEE PRIOR COMMENT #S21.
PROVIDE CTS LETTER/RESPONSE FOR REVIEW,NO CTS LETTER ATTACHED.
S10. SEE PRIOR COMMENT #S22.
NO ATTACHED CTS LETTER PLEASE PROVIDE FOR REVIEW.
See prior Comments dated 10/7/03.
If you should have questions on these Comments, please call Douglas Laakso, Structural Plans Examiner at (520)791-5550 x 1111.
11/05/2003 DOUG WILLIAMS ENGINEERING REVIEW Denied Building plans may not be approved prior to Site Plan approval.
11/13/2003 Daniel Castro ZONING REVIEW Denied Zoning Review may not approve structural plans until the site plan is approved by all sections and the structural plans have been approved by Building Review.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/25/2003 LISA LESNY OUT TO CUSTOMER Completed
11/24/2003 ANGIE SHOFFSTALL REJECT SHELF Completed