Review Details: COMMERCIAL TI

Permit Number - T02CM05787
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/23/2003 MARTIN HAEBERLE WATER REVIEW Approved
01/23/2003 MARTIN HAEBERLE PLUMBING-COMMERCIAL REVIEW Denied 1. Indicate on plans a permanently fixed ladder for the water heater. Reference section 511.2 UPC
2. Provide plumbing layout on floor plan including fixture count calculations.
3. Water heater pressure relief drain to terminate to the outside or an approved location. Show on plans. Reference section 608.5 UPC
01/23/2003 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Denied 1. Provide structural design calculations for suspended gypsum ceiling.
2. Plans indicate the use of wood framed headers. The building is a Type II building requiring structural members to be non-combustible. Revise plans as needed. Reference section 603.1 IBC.
3. Please complete special inspection agreement prior to issuance of permit
01/23/2003 MARTIN HAEBERLE MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide outside air calculations and method of achieving it. Reference section 403.3 IMC
2. Show condensate line, including overflow line, for air handler on floor plan and show termination. Reference section 307 IMC
01/28/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT LBUCZYN1@CI.TUCSON.AZ.US
IF YOU CARE TO DISCUSS.

Sheet E2.0
1. It appears that the minimum clearance requirements are not met for the surface mounted panel "M" at 277 V-G, with live electrical parts on either side, needs 4' per Table 110-26(a).
2. Specify fuse size in fused disconnect for fan coil unit as 2-1/4 amp. Add a note: "All HVAC equipment shall be protected per manufacturer's specifications/nameplate information."
3. Not a code issue, but VAs on Phases A, B, & C of Panel B do not line up with VAs on Phases A, B, & C of Panel A, as it feeds B.
02/04/2003 GERRY KOZIOL WWM REVIEW Approved
12/17/2002 PETER MCLAUGHLIN ZONING REVIEW Approved
12/17/2002 DOUG WILLIAMS FLOODPLAIN REVIEW Approved
12/18/2002 JIM EGAN FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/04/2003 MONICA VALDEZ OUT TO CUSTOMER Completed