Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T02CM05787
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/23/2003 | MARTIN HAEBERLE | WATER | REVIEW | Approved | |
01/23/2003 | MARTIN HAEBERLE | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Indicate on plans a permanently fixed ladder for the water heater. Reference section 511.2 UPC 2. Provide plumbing layout on floor plan including fixture count calculations. 3. Water heater pressure relief drain to terminate to the outside or an approved location. Show on plans. Reference section 608.5 UPC |
01/23/2003 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Provide structural design calculations for suspended gypsum ceiling. 2. Plans indicate the use of wood framed headers. The building is a Type II building requiring structural members to be non-combustible. Revise plans as needed. Reference section 603.1 IBC. 3. Please complete special inspection agreement prior to issuance of permit |
01/23/2003 | MARTIN HAEBERLE | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide outside air calculations and method of achieving it. Reference section 403.3 IMC 2. Show condensate line, including overflow line, for air handler on floor plan and show termination. Reference section 307 IMC |
01/28/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT LBUCZYN1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS. Sheet E2.0 1. It appears that the minimum clearance requirements are not met for the surface mounted panel "M" at 277 V-G, with live electrical parts on either side, needs 4' per Table 110-26(a). 2. Specify fuse size in fused disconnect for fan coil unit as 2-1/4 amp. Add a note: "All HVAC equipment shall be protected per manufacturer's specifications/nameplate information." 3. Not a code issue, but VAs on Phases A, B, & C of Panel B do not line up with VAs on Phases A, B, & C of Panel A, as it feeds B. |
02/04/2003 | GERRY KOZIOL | WWM | REVIEW | Approved | |
12/17/2002 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
12/17/2002 | DOUG WILLIAMS | FLOODPLAIN | REVIEW | Approved | |
12/18/2002 | JIM EGAN | FIRE | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
02/04/2003 | MONICA VALDEZ | OUT TO CUSTOMER | Completed |