Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T02CM05764
Parcel: 133153390

Address:
1865 N KOLB RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T02CM05764
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/07/2003 RAUL PALMA BUILDING-COMMERCIAL REVIEW Denied City of Tucson, Development Services
BUILDING AND STRUCTURAL COMMENTS


1) Provide a 1-hr wall separation between the gas storage room and the office space.
Provide a detail of the 1-hr wall. Also, provide a 1-hr door. Sec. 414.2 & 414.2.1
01/23/2003 PATRICIA GEHLEN ZONING REVIEW Denied Zoning
1/23/2003
Zoning comments on the white card have not been addressed. Prior to approval, sufficient on-site parking for this and all tenants must be documented.
01/30/2003 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Denied 1.M-15 load is not accurate s/b 1620 watts. 2.Is M-17 load 10 amps?(E-1),Panel schedule (E-3) indicates load as 6.6 amps? please clarify.3.M-29 load is missing from panel schedule. 4.Describe cir. M-41.(E-1),load ? 5.Indicate M-24 load at panel schedule(e-3).6.M2-2 breaker s/b a 2pole breaker not a single pole.(E-3). 7. M-29 load is missing at panel schedule (E-3). 8.Indicate exit lighting wattages and exh. fan loads. 9.Properly calc. load on cir.M-10.(E-3,E-2). 10. Recalculate load on panels M,M2 after all corrections made. 11. Update service loads(E-3). 12.Revise M.E.C. calcs. after all corrections made to loads(E-2,E-3).
02/03/2003 MARTIN HAEBERLE PLUMBING-COMMERCIAL REVIEW Denied 1. Provide water pressure and water pipe sizing calculations. Reference Appendix A, UPC.
2. Coordinate plumbing schedule, plans, and riser diagrams.
3. Coordinate water heater detail with plans and riser diagrams. Indicate height of water heater platform.
4. Verify that the effluent of the equipment drains (air compressor and vacuum pump) complies with Section 307.0, UPC.
02/03/2003 ROBERT SHERRY WATER REVIEW Approved
02/03/2003 MARTIN HAEBERLE MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide approved combination fire/smoke dampers for protection of ducts and penetrations of fire resistive walls at gas storage room. Reference Section 715, IBC.
2. Provide calculations verifying compliance with requirements for medical gas storage rooms. Reference Sections 501, 502.7, and 502.8, IMC and, Section 3006, IFC
3. Coordinate design of gas storage room with architectural design, sheet A1.
4. Provide energy code compliance calculations.
5. Provide duct smoke detector for HP-1. Reference Section 606.2.1
6. Provide calculations demonstrating adequate ventilation. Reference Section 401, IMC.
7. Provide heating capacities for rooftop units.
8. Revise plans as required to provide a separation of at least ten feet between air intake openings and exhaust openings. Reference 401.5, IMC.
12/16/2002 GERRY KOZIOL WWM REVIEW Approved
12/18/2002 JIM EGAN FIRE REVIEW Approved
12/18/2002 DOUG WILLIAMS FLOODPLAIN REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/05/2003 ELAINE ROSE OUT TO CUSTOMER Completed