Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T02CM05702
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/18/2003 | JIM EGAN | FIRE | REVIEW | Denied | NEEDS SITE PLAN SUBMITTED WITH BUILDING PERMIT SET. |
| 03/20/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide site plan showing location of water meter and backflow preventer, gas meter, inverts and slope of building sewer, flood rim of upstream manhole, and floor elevation. Reference Section 302.3, Uniform Administrative Code 1994. 2. Coordinate plumbing plans and isometrics for both water and sewer with floor plan. Four fixtures are shown on the floor plan (water closet, lavatory, urinal, and shower) but only three fixtures are connected on the plumbing plan (water closet, lavatory, and urinal) and three fixtures on the isometrics (water closet, lavatory, and shower). Reference Section 302.3, Uniform Administrative Code 1994. 3. Complete the sewer schematic, showing the sizes of all pipe sections. Reference Section 302.3, Uniform Administrative Code 1994. 4. Complete the natural gas calculations. Reference Section 302.3, Uniform Administrative Code 1994. 5. Provide complete water supply calculations per Section 610.7, UPC 1994. Include all fixtures (including hose bibb) in the calculations. 6. Verify size of RPBP after meter complies to Section 610.2, UPC 1994. 7. Provide detail of water heater installation, including excess pressure relief, expansion tank, and valves. Reference Section 302.3, Uniform Administrative Code 1994. 8. What type of fuel is being used? The water heater is noted as being fueled with natural gas on sheet 7 and propane on sheet 8. 9. Show routing and termination of T&P relief piping. Reference Section 608.5, UPC. 10. Provide CW shut off valves for each building entrance. Reference Section 605.3, UPC. 11. Provide location and sizing information for gutters and downspouts. Reference Appendix D, UPC. 12. Show size, routing, and termination of drain and overflow from evaporative cooler, EC-1 |
| 03/20/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide complete energy calculations. 2. The evaporative cooler, EC-1, has 60 CFM ducted to the restroom and 125 CFM ducted to storage room 2. Where does the remaining 4,265 CFM go? 3. Provide ventilation for storage room 1. Reference Section 401.2, IMC 2000. 4. Protect duct penetrations of any fire partitions or smoke barriers as required in Section 607.5, IMC 2000. 5. Provide information to demonstrate compliance to Section 1102.1, IMC 2000. 6. Show how the condensers COMP-1 and COMP-2 are mounted and protected from damage. Reference Sections 304.8 and 1101.3, IMC 2000. 7. Provide combustion air openings into water heater enclosure per Section 703.1.1, IMC 2000. 8. Show size, route and termination of the water heater vent. Reference Section 512.0, UPC 1994. |
| 03/20/2003 | GERRY KOZIOL | WWM | REVIEW | Denied | |
| 03/20/2003 | ROBERT SHERRY | WATER | REVIEW | Denied | Provide site plan. |
| 03/21/2003 | ANY | FLOODPLAIN | REVIEW | Approved | |
| 04/15/2003 | PATRICIA GEHLEN | ZONING | REVIEW | Denied | need approved site plan |
| 04/17/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | The Code of the State Board of Technical Registration ARTICLE 3. REGULATORY PROVISIONS. 32-143 Exceptions, states: A registrant under this chapter may engage in practice in another category regulated pursuant to this chapter only to the extent that the person is qualified and to the extent that the work may be necessary and incidental to the work of the registrant's profession on a specific project. This exception does not apply to public works projects. Based upon my review and in accordance with the State Board of Technical Registration Rules, this plan should be designed and sealed by an Arizona registered professional electrical engineer. TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT LBUCZYN1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS. 1. Please submit fixture cut sheets. Fixture AA does not appear to be listed for outdoor application/wet locations. 2. Note that outdoor fixtures shall comply with the Outdoor Lighting Ordinance. 3. Regarding Note #3 beneath the panel schedule, incandescent exterior lighting is not permitted, 1998, IECC, 705.5. 4. Keynote #2, Condenser Unit, lacks coordination with Mechanical Plan, where it is referred to as a Compressor unit. Provide voltage and phase requirements for this motor load. 5. Provide overload protection for the unit above per NEC Article 430 Part C. 6. Provide conductor and conduit sizing for the unit above per NEC Article 310 and Article 430 Part B. 7. Provide Ground-Fault and Short Circuit protection for the above unit per NEC Article 430 Part D. 8. Specify the parameters of the disconnects for this unit, such as voltage and current rating, enclosure rating, and number of poles. 9. Same as Comments 3-6 for the piece of equipment referred to as "Compak Unit Coolers" on Sheet 8 and "Evaporator Unit" on Sheet 9. 10. Provide Ground-Fault and Short Circuit protection for EC-1 per NEC Article 430 Part D. 11. Same as Comments 4-6 for the Water Heater. 12. Referring to Panel A, 2890V is not available TEP service. Please correct, or justify otherwise. In any case, if VL-L is 2890, VL-N would NOT be 360. 13. Fill out the "BKR" column on panel schedule. 14. Regarding the notation on the Riser Diagram "Ground per 250-80", 250-81, 83, the NEC goes from 250-80 to 250-84. No 250-81. No 250-83. 15. Indicate voltage of service. 16. Indicate available fault current at service. Provide for appropriate ratings of equipment. 10,000 withstand rating on Panel A is suspect. |
| 04/28/2003 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Structural Engineer of record to seal structural plans. 2. Provide complete structural calculations, i.e. interior foundation, retaining walls, and glulam beams. 3. Accessible bathroom does not match accessible details. Revise floor plan to be in compliance with detail. 4. Proposed shower is to be accessible. Provide details. Reference section 1108.2 IBC 5. Indicate firewall ratings and required penetration protection. 6. Fire wall parapet to extend a minimum of 30 inches above roofline. Reference section 705.6 IBC 7. How is attic ventilation being achieved? Reference section 1202.2 IBC 8. Special Inspection required for concrete. Provide special inspection agreement forms prior to permit issuance. 9. Exit discharge by a ramp is required to be a minimum of 10 feet from lot lines. References section 1006.2.2 IBC. Revise plans 10. Ramp, change in direction, landings are required to be a minimum of 60" by 60" Reference section 405.7.4 ANSI A117.1 Revise plan note see site plan 11. Provide handrails on both sides of ramps. Reference section 405.8 ANSI A117.1 12. Guardrail height shall be a minimum of 42 inches per section 1003.2.12.1 IBC. Revise plan 13. Ramp landings to extend a minimum of 60 inches. Reference section 405.7.3 ANSI A 117.1 Revise floor/site plan |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/28/2003 | MONICA VALDEZ | OUT TO CUSTOMER | Completed |
| 04/28/2003 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |