Permit Number: T02CM05702
Parcel: 120086800

Address:
4762 S 12TH AV

Review Status: Completed

Review Details: SITE

Permit Number - T02CM05702
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/08/2003 JOE LINVILLE LANDSCAPE REVIEW Denied The loading area must be screened from view along 12th Avenue per LUC Table 3.7.2-I. A six-foot high masonry screen wall is required.

A minimum five-foot high masonry screen wall is required along the entire west property line. LUC Table 3.7.2-I

A covenant is required related temporary use of the MS&R right of way area along S.12th Avenue. LUC 2.8.3.5.F

If more than four parking spaces are required for the site, a minimum of one canopy tree must be provided per LUC 3.7.2.3.

Revise the planting plan to relocate or eliminate plants that exceed 30" in height.
01/08/2003 JOE LINVILLE NPPO REVIEW Approved exception per 1998 PC aerial.
01/28/2003 PAUL MACHADO ENGINEERING REVIEW Denied To: Architectos E.J. Ornelas & Assoc.
Eduardo Ornelas, Architect
100 N. Stone Avenue
Tucson, Arizona 85701

SUBJECT: 4762 S. 12th Avenue
Site plan T02CM05702 (First Review)
T14S, R13E, Section 35

RESUBMITTAL REQUIRED: Site Plan.

The Site Plan (SP) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Site Plan:

1. This project was reviewed for full code compliance.
2. Please provide property description per D.S. 2-02.2.1.3.5
3. Please label all vehicular, bicycle, pedestrian, and handicapped circulation clearly identified per D.S. 2-02.2.1.12.
4. The few spot elevations provided suggest that the drainage will flow away from the landscape border. Water harvesting should be provided down grade as the Drainage Statement suggests.
5. Please provide Drainage patterns and finished grades per D.S. 2-02.2.1.16.
6. Please list estimated cut & fill quantities per D.S. 2-02.2.1.17.
7. Dimension from street monument lines to existing and proposed curbs, sidewalks, driveways, and utility lines per D.S. 2-02.2.1.21.
8. Please provide existing topographic contours at intervals not exceeding two (2) feet and/or spot elevations as pertinent and Bench Mark based on City of Tucson Datum, including City Field Book and page number per D.S. 2-02.2.1.23.
9. Show refuse container location, size, and access thereto fully dimensioned per D.S. 2-02.2.1.32 and D.S. 6-01.0 or provide an approval letter form from solid waste for the use of roll-outs.
10. Please provide adjacent property grades for review in accordance with in 2000 IBC section 13 concerning fills.
11. A private improvement agreement may be necessary for any work performed within the Right-of-way. Contact Department of transportation at (520) 791-4249 for permit information.
12. Please show a typical cross section of the P.A.A.L. or call out the percentage of slopes. Call out the GB at the D/W, if applicable.
13. Please show the proposed roof drainage patterns, 100% of the 10-year flow must be conveyed under the sidewalks. Please provide supporting calculations to demonstrate compliance with D.S. 3-01.4.4. If the location(s) of the roof scuppers have not yet been decided, a general note indicating sidewalk scuppers (per COT/SD) will be used when the roof scuppers locations have been designed will suffice.
14. Add note: "Depress all landscaped areas 6" maximum for water harvesting".

Drainage Statement:
1. The drainage statement is approved.

If you have any questions, I can be reached at 791-5550 or pmachad2@ci.tucson.az.us
Paul Machado
Senior Engineering Associate,
01/28/2003 ANY FLOODPLAIN REVIEW Approved
01/28/2003 ANY SANITATION REVIEW Denied To: Architectos E.J. Ornelas & Assoc.
Eduardo Ornelas, Architect
100 N. Stone Avenue
Tucson, Arizona 85701

SUBJECT: 4762 S. 12th Avenue
Site plan T02CM05702 (First Review)
T14S, R13E, Section 35

RESUBMITTAL REQUIRED: Site Plan.

The Site Plan (SP) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Sanitation:

1. Show refuse container location, size, and access thereto fully dimensioned per D.S. 2-02.2.1.32 and D.S. 6-01.0 or provide an approval letter form from solid waste for the use of roll-outs.



pmachad2@ci.tucson.az.us
Paul Machado
Senior Engineering Associate,
12/16/2002 JIM EGAN FIRE REVIEW Approv-Cond FIRE APPROVAL FOR FIRE HYDRANT LOCATION AND ACCESS ONLY.
12/31/2002 PETER MCLAUGHLIN HANDICAP-SITE REVIEW Approved
12/31/2002 PETER MCLAUGHLIN ZONING REVIEW Denied SITE PLAN TRANSMITTAL

TO: Eduardo Ornelas
100 N. Stone Avenue
Tucson, AZ 85701
(520) 624-8102

FROM: Peter McLaughlin
Senior Planner
Development Services Dept.


FOR: Patricia Gehlen
Principal Planner
Development Services Dept.

PROJECT:
T02CM05702
Cold Storage and Office for El Rey del Elote
4762 S. 12th Avenue
Site Plan Review (1st review)

TRANSMITTAL: December 31, 2002


COMMENTS: Please attach a response letter with the next submittal, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.


1. This project was reviewed as a change of use/new building. Full code compliance is required.
DS 2-02
2. Please clarify the proposed principal use and existing use of the site. The parking calculations indicate a wholesale use (parked at 1 vehicle space per 2,000 square feet) is proposed, but the title block indicates office (1/200)and commercial storage (1/5,000) uses. Delineate the office and storage areas within the proposed building and provide the square footage for each use on the site plan. Parking calculations may not be verified as being accurate until the principal use is specified.
DS 2-02.2.1.A.31
3. Revise adjacent zoning to the west to read "R-1" rather than "R-2".
DS 2-02.2.1.A.28
4. The proposed location of the loading zone, and the size of the site, will not enable trucks to maneuver to turn around and exit the site. Vehicles/trucks may not back out onto 12th Avenue, which is a designated MS&R. Please revise plan drawing.
LUC 3.4.4.2.A.1
LUC 3.4.5.2
DS 2-02.2.1.A.14
DS 2-02.2.2.A.5

5. Provide a proposed floor area ratio (FAR) calculation to the plan. The FAR is calculated as the building gross floor area ÷ site area. In this case, the FAR would be calculated as 1,700 sq ft GFA ÷ 8,480 sq. ft. = 0.20. As stated on the plan, the maximum allowed FAR per development designator 31 is 0.90.v
DS 2-02.2.2.A
6. Provide the development designator "31". If the proposed use is commercial storage, it is subject to LUC 3.5.10.1 (Please demonstrate compliance on site plan-motion sensor lights and all other lighting may not be directed towards residentially zoned properties). If the proposed use is wholesaling there are no "subject to" restrictions. If the proposed use is administrative and professional office, it is subject to LUC 3.5.13.5. Please add a note stating the applicable restrictions.
LUC 2.5.4.2

7. The west lot line perimeter yard building setback (adjacent R-1 zoning) is required to be 1-1/2 times the height of exterior building wall. The west lot line building setback dimension shows only between 5 feet and 6 feet on the drawing. In the table it is stated that a 65- foot bldg. is provided to the west property line. Please revise. An LDO will be required if the proposed building does not meet perimeter yard bldg. setback requirements. To verify required bldg. setback, provide the proposed height of structure wall above finished grade elevation along the west side of the building. The setback table also indicates that only 45 is provided as a street yard building setback. It appears that the provided street yard bldg setback is greater than 45 feet. Please clarify. Also, please clarify that the required street yard building setback is actually the greater of 21 feet or (H) measured from back of future curb location.
LUC 3.2.6.4
LUC 3.2.6.5


8. If easements exist on the site, please dimension their width, state their purpose, and place the recordation information, including docket and page reference numbers on the site plan. DS 2-02.2.1.A.20

9. If there are any billboards on site, please demonstrate compliance with LUC 3.5.4.26. LUC 2.5.4.2.A.5


10. Please show the location, size and height of any proposed free-standing signs.
DS 2-02.2.1.A.13
11. Provide a note stating that any required screening, landscaping or other improvements which are located in the future right-of-way will be relocated at time of 12th Avenue widening at no expense to the City of Tucson. LUC 2.8.3.5.C.3

12. A pedestrian refuge are must be provided between the front of the building and the PAAL. Where loading dock doors are not proposed a five foot wide pedestrian refuge area with a minimum four-foot wide sidewalk is required between buildings and PAALs. The refuge areas must include a four-foot wide concrete sidewalk that is physically separate from the PAAL. To clarify, please show the location of all entrance doors, including the loading door. DS 2-02.2.1.A.12
DS 3-05.2.2.B.1


If you have any questions about this transmittal, please call Peter McLaughlin, (520) 791-5608.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/27/2003 DELMA ROBEY OUT TO CUSTOMER Completed