Permit Number: T02CM05644
Parcel: 106022570

Address:
327 W KING RD 01

Review Status: Completed

Review Details: 3RD PARTY REVIEW-COMMERCIAL

Permit Number - T02CM05644
Review Name: 3RD PARTY REVIEW-COMMERCIAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/04/2003 EROSE1 FIRE REVIEW Needs Review
04/04/2003 EROSE1 WATER REVIEW Needs Review
04/04/2003 GP 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied ARCHITECTURAL COMMENTS
General
Sheets 2.1, 2.2, 2.3, 6P.1, 6P.2 and 6.2 are missing from the plan set. Please provide these sheets.

Sheet 1.1
1. Keynote 23, which references accessibility criteria for landings, is not shown on the plan. Please keynote where this condition occurs.

2. Specify the item number from IBC 719.1(2) for the fire resistant wall called out in keynote 5 or provide the listing from an approved testing agency.

3. The water closet in floor plan B must be a maximum of 18" from the water closet centerline to the side wall. Ref. ANSI A117.1, 604.2.
Sheet 1.2
4. Rooms appear to be mislabeled in the overall floor plan B. Please revise.

Sheet 1.3
5. A number of details on this sheet have been crossed out implying they are not to apply. Please clarify.

Sheet 1.4
6. Elevation drawings, noted at 1/4" = 1"-0", do not appear to be to scale please clarify.

7. The CMU graphic is not shown in elevation C. Please revise.

Sheet 1.5
8. The details 3/6.2 and 5/6.2 are on a sheet that was not included in the plan set. Please provide this sheet.

Sheet 3.1
9. Show the landing at the exterior doors.

Sheet 6.1
10. Detail 6/6.1 is mislabeled as a 3 coat stucco system. San-Kote is a 2 coat system. In the detail, state that the stucco system is to be prepared and installed in accordance with the attached ICBO report # ER5144.

11. Please note that the Simpson H25 connectors at the joist to beam connections are at each joist as specified in detail 8/5.3.

12. Please note that fire blocking and draft stopping will be provided in accordance with IBC 716.


STRUCTURAL COMMENTS
General
13. Coordinate with mechanical comment #1.

14. Please specify the grades and species for the posts and trimmers.


PLUMBING COMMENTS
Sheet 15.1
15. Show the ABS line size from the shower drains. Ref. UPC 703.

16. Show the vents and sizing. Ref. UPC Table 7-5

17. Label the 2-way cleanout adjacent to the office area.
18. Note ABS piping to be schedule 40 DWV. Ref. UPC 701.

19. Show the location of temperature and relief valves, drains and points of termination. Ref. UPC 608.

Sheet 15.2
20. Show vent sizes on the isometric drawings. Ref. UPC Table 75.

21. Clarify if floor drains are to be provided for accessible showers. Ref. UPC 410.


MECHANICAL COMMENTS
Sheet 15.3
22. Clarify note 1 which appears to refer to the plumbing code.

23. Show the provisions for condensate disposal. Ref. IMC 307.

24. Please revise note 5 to reference the 2000 IMC.

25. Verify structural adequacy of framing members with respect to the concentrated loads of the roof top equipment specified.


ELECTRICAL COMMENTS
Sheet 16.1
26. Provide means of egress illumination. Ref. IBC 1003.2.11.

27. Note the dryer circuits as B6 & B8 and the washer as B9.

28. Circuits B10 and B12 do not appear to have been used. Please clarify.

29. Coordinate the electrical fixture schedule designations with the fixtures shown on the plan.

30. Show the circuit used for the interconnected, battery backed-up smoke alarms. Ref. IBC 907.2.10.

31. Service B one line diagram indicates 3 sub-panels, but only 2 sub-panels are calculated. Please clarify.

32. Show keynote 3 specifying thermostat location on the plan.




ENERGY COMMENTS
General
33. Please coordinate energy code compliance information in plan information to correspond with Sheet 15.3.
04/04/2003 EROSE1 FLOODPLAIN REVIEW Needs Review
04/04/2003 PETER MCLAUGHLIN ZONING REVIEW Needs Review
04/04/2003 EROSE1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
04/04/2003 ELAINE ROSE OUT TO CUSTOMER Completed