Permit Number: T02CM05613
Parcel: 12511055A

Review Status: Completed

Review Details: SITE

Permit Number - T02CM05613
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/06/2003 BLANCA ESPINO ENGINEERING REVIEW Denied Site Plan
1. Indicate roof slope and downspouts. D.S. 2-02.2.1.6

2. Indicate existing and future sight visibility triangles for all local streets and driveway. D.S. 2-02.2.1.10

3. The proposed loading space is measured at 12' x 32'. The required loading space is 12' x 35'. Please make correction. Demonstrate and dimension vehicle maneuverability area. D.S. 2-02.2.1.14

4. Indicate estimated cut and fill quantities on site plan. If the amount of cut and fill equals fifty (50) cubic yards or more, a grading plan review/permit will be required. D.S. 2-02.2.1.17

5. Indicate if streets are "Public or Private". D.S. 2-02.2.1.18

6. Indicate dimensioned existing and future right-of-way, including any applicable Major Streets and Routes (MS&R) Plan right-of-way. The Alvernon Way & Speedway Blvd. intersection is a widening intersection, therefore, Alvernon Way future right-of-way is 120' with a widening width of 150' the first three hundred (300) feet then tapering off at 120' another three hundred (300) feet. Please make correction. D.S. 2-02.2.1.19

7. Indicate dimensioned all existing and proposed curbs, sidewalks, driveways and utility lines. D.S. 2-02.2.1.21

8. The refuse container location is an appropriate area. Relocate refuse container. Dimensioned size and demonstrate vehicle maneuverability area. D.S. 2-02.2.1.32

9. A sidewalk is required to the north of the property.

10. All parking spaces are to be 8' x 18'. Please make corrections
01/06/2003 BLANCA ESPINO FLOODPLAIN REVIEW Denied SEE ENGINEERING COMMENTS.
01/06/2003 BLANCA ESPINO SANITATION REVIEW Denied SEE ENGINEERING COMMENTS.
01/07/2003 JOE LINVILLE LANDSCAPE REVIEW Denied The proposed location of the refuse enclosure is not acceptable. Per LUC Table 3.7.2-I refuse storage areas are to be buffered from the street with a minimum ten-foot wide landscape border.

The decorative wall proposed within the Alvernon Way landscape border requires modification in order to comply with LUC 3.7.3.2.C, which governs acceptable locations for walls within the landscape borders. Revise as necessary to comply.

The loading zone must be screened per LUC Table 3.7.2-I. A minimum six-foot high masonry wall is required between Alvernon Way and the loading area.

The site landscaping must comply with LUC 3.7.2.2.C which restricts the use of plants not listed on the ADWR Plant List (DS 9-06). Revise the plans as necessary comply with the oasis provisions of the code. See also DS 2-06.3.2. for additional requirements.

The submittal did not include information regarding compliance with LUC 3.8 Native Plant Preservation. Identify any existing protected plants located on the site. If applicable submit an NPPO application for exception.
01/07/2003 JOE LINVILLE NPPO REVIEW Denied The submittal did not include information regarding compliance with LUC 3.8 Native Plant Preservation. If applicable submit an NPPO application for exception.
12/09/2002 JIM EGAN FIRE REVIEW Approved
12/17/2002 PETER MCLAUGHLIN HANDICAP-SITE REVIEW Denied See zoning review comments
12/17/2002 PETER MCLAUGHLIN ZONING REVIEW Denied TO: Metro Permit Express
1010 N. Alvernon Way
Tucson, AZ 85711
(520) 977-7187

FROM: Peter McLaughlin
Senior Planner

FOR: PATRICIA GEHLEN
Principal Planner
Development Services Dept.
PROJECT:T02CM03236
Professional Office
1001 N. Alvernon Way
Site Plan Review (1st review)

TRANSMITTAL: December 17, 2002

COMMENTS: Please attach a response letter with the next submittal, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed. CODE SECTION/ DEVELOPMENT STANDARD

1. This project is being reviewed as a full code compliance review.
DS 2-02
2. Wheelstops, where provided, must be dimensioned at two-and-one-half (2½) feet from their front side (towards the tire when a car is parked) to the front end of overhang area. At least 15 ½ feet (measured from the front of wheelstops) in depth must be provided for each parking space. Please revise site plan drawing and parking detail.
DS 3-05.2.3.C.2
3. Add all street monument lines, including ROW widths for Alvernon Way (MS&R) First Street and Second Street Per MS&R Plan, Alvernon Way has an MS&R full right-of-way of 120 feet. Also, add sight visibility triangles at the access drive to Alvernon Way and at the intersections of Alvernon with First Street and with Second Street.
DS 2-02.2.1.A.10 & 19

4. Revise adjacent zoning to indicate that a portion of the site to the west is zoned O-3 (at the southwest corner of site).
DS 2-02.2.1.A.28
5. Replace the word "coverage" with Floor Area Ratio (FAR) in the calculation and remove the lot coverage information. Add to the FAR calculation a statement that the maximum allowed FAR is 0.5
DS 2-02.2.2.A.2

6. State the existing use on the site plan (i.e. vacant).
DS 2-02.2.1.A.31
7. A minimum setback of one (1) foot is required between an open structure such as a carport and a PAAL. The 1-foot setback is measured from the closest edge of the canopy overhang to the PAAL. Please revise carport setback from PAAL and provide the proposed height and dimensions of of carport structures.
DS 3-05.2.2.B.2
DS 2-02.2.1.A.6
8. Revise building setbacks to indicate that the required street perimeter yard building setback from Alvernon Way (MS&R) is the greater of 21 feet or the height of the structure measured from the back of future/existing curb location. Revise the building setback provided to the west lot line to indicate the setback of the proposed carport shown on the site plan. Revise the required building setback to the north and south to be the greater of 21 feet or the height of structure, measured from outside edge of nearest travel lane along First Street and Second Street respectively. Revise the building setback provided to the north lot line to indicate the setback of the proposed carport shown on the site plan (measured from outside edge of nearest travel lane). Revise the building setback provided to the south lot line to indicate the setback of the proposed office building (measured from outside edge of nearest travel lane).
DS 2-02.2.1.A.7
LUC 3.2.6.5

9. Because proposed bicycle parking is located toward the rear of the building from Alvernon Way, provide directional signage indicating the location of class 2 bicycle parking. Show the location of the directional signage on the site plan. DS 2-09.5.1

10. If any easements exist or are proposed show their location on the site plan along with their dimensioned width, their purpose and the recordation information (docket and page). DS 2-02.2.1.A.20

11. Because the legal description describes a portion of a lot, provide a 20-year history of the lot or documentation of lot split approval from the zoning review section.
12. If any free-standing outdoor lighting or signage is proposed for this site, please detail on the site plan.
DS 2-02.2.1.A.13 & 25
If you have any questions about this transmittal, please call Peter McLaughlin, (520) 791-5608.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/08/2003 TAMI ACHONG OUT TO CUSTOMER Completed