Permit Number: T02CM05572
Parcel: 13015001A

Address:
4646 E 22ND ST

Review Status: Completed

Review Details: 3RD PARTY REVIEW-REVISION/OTHER

Permit Number - T02CM05572
Review Name: 3RD PARTY REVIEW-REVISION/OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/09/2003 WILDAN 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied GENERAL COMMENTS:

1. This project has been reviewed for conformance with the 2000 IBC, 1997 UAC, 2000 IMC, 1998 IECC, 1999 NEC codes with local modifications and the 1994 UPC with State of Arizona Amendments. Any revisions to this plan will require an additional review and approval by Willdan.

2. The submittal documents show no evidence of having been reviewed and accepted by the design professional in responsible charge. The metal building manufacturer as a product supplier is responsible for its product, but it is not the engineer of record for the project. Deferred design submittals shall first be reviewed and accepted by the design professional in responsible charge for the project before submittal to the building official or its designated representative, Willdan. Please obtain the required review and approval before resubmittal to Willdan. Reference IBC Section 106.3.4.2