Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T02CM05552
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/11/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Note 9 and the revised note 14 on sheet 3M1 are contradictory; please revise. 2. Coordinate mechanical components listed in Summary Compliance Report with equipment specified on drawings. Second request. |
| 04/11/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Indicate the slope of the new building sewer. Reference Section 718.1, UPC. 2. Revise keynote 16 to indicate that the bypassed natural gas pipe is to be abandoned in place. Reference Section 1211.3, UPC. 3. Indicate the inverts of the new building sewer at its points of connection to the existing building sewer as well as its minimum slope. Reference Sections 718.1 and 718.3, UPC 1994. Second request. 4. Coordinate stack and riser diagram with floor plan. Second request. 5. Coordinate natural gas calculations with heating capacity of rooftop units on mechanical plans. Second request. 6. Termination of the excess pressure relief from the water heater over service sink S-1 is not approved location. Reference Section 608.5, UPC 1994. 7. Provide design of mounting method for suspended water heater. Indicate height of water heater platform. Reference Section 302.3, Uniform Administrative Code 1994. 8. No shut off valve may be located between the water heater and the thermal expansion tank. Reference Section 608.3, UPC 1994. |
| 05/05/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 05/06/2003 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Denied | #1. See Duffy School comments #3 See Duffy school comments |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/07/2003 | TAMI ACHONG | OUT TO CUSTOMER | Completed |