Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T02CM05551
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/11/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Note 9 and the revised note 14 on sheet 3M1 are contradictory; please revise. 2. Coordinate mechanical components listed in Summary Compliance Report with equipment specified on drawings. Second request. |
| 04/11/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Indicate the inverts of the new building sewer at its points of connection to the existing building sewer and to the HCS as well as its minimum slope. Reference Sections 718.1 and 718.3, UPC 1994. Second request. 2. Coordinate stack and riser diagram with floor plan. Second request. 3. Coordinate natural gas calculations with heating capacity of rooftop units on mechanical plans. Second request. 4. Termination of the excess pressure relief from the water heater over service sink S-1 is not approved location. Reference Section 608.5, UPC 1994. 5. Provide design of mounting method for suspended water heater. Indicate height of water heater platform. Reference Section 302.3, Uniform Administrative Code 1994. 6. No shut off valve may be located between the water heater and the thermal expansion tank. Reference Section 608.3, UPC 1994. 7. New section of waste line revised from 6" to 4" on sheet 1MP1 but not revised on sheet 1P1; please coordinate drawings. |
| 04/21/2003 | GERRY KOZIOL | WWM | REVIEW | Denied | New 4" private sewer needs to connect to a manhole either new or existing (fronts 15" is public sewer) |
| 05/05/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 05/06/2003 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Denied | 1.A deferred submittal requires approval of the Building Official. Submit in writing a request for deferral of the metal building plans to the Building Official. A letter is needed seperate from the response letter. You may put all 4 projects on one letter. Please include permit numbers and approximate date of the deferred submittal. 2. Complete the assumed property line between buildings or include allowable area calculations for adjacent structures. References section 704.3 IBC. Area calculations provided do not include existing structures. reference section 503.1.3 IBC. Clarify location of assumed property line and rating of exterior walls if calculations are not to be revised 3. Provide existing and new buildings plumbing fixture count showing compliance with the total fixtures required per Table 2902.1 IBC As per agreement with TUSD and Dave Mann, Building Official. If calculations are not provided as requested the new building must include required plumbing fixtures as per Table 2902.1 IBC Revise Plan |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/07/2003 | TAMI ACHONG | OUT TO CUSTOMER | Completed |