Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T02CM05528
Parcel: 123060190

Address:
2033 E LEE ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T02CM05528
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/27/2002 TERRY STEVENS BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T02CM05528
12/16/02 2ND REVIEW 12/27/02
PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

GENERAL REQUIREMENTS:

1. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

2. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.

3. ALL ENGINEERS AND ARCHITECTS INVOLVED IN THE DESIGN OF THE STRUCTURE ARE TO SEAL THE
RELATED SHEETS OF PLANS, DETAILS AND CALCULATIONS. THIS IS IN ACCORDANCE WITH THE RULES OF
THE STATE BOARD OF TECHNICAL REGISTRATION.

SITE PLAN:

1. PLANS RESUBMITTED DO NOT HAVE THE APPROVAL STAMPS FROM WASTE WATER, ZONING, OR FLOOD PLAIN

STRUCTURAL PLANS:

1. INDICATE [ DEPTH ]HEIGHT OF ALL LINTELS ---DETAIL 2/A400-----THIS DIMENSION IS REFERENCED TO WINDOW SCHEDULE WHICH DOES NOT INDICATE DEPTH OF LINTEL-------REFERENCE TO IRC IS NOT ADEQUATE

2. DETAIL 4/A400-------- INDICATE HANGER FOR I-JOISTS FOR SIDE WITH NEW LEDGER

ELECTRICAL PLANS:

1. AT LEAST ONE WALL SWITCH CONTROLLED LIGHT OR OUTLET MUST BE PROVIDED AT OUTDOOR ENTRANCES OR EXITS PER E3801.----------A LIGHT IS REQUIRED OUTSIDE OF THE DOOR

2. A RECEPTACLE OUTLET SHALL BE PROVIDED ADJACENT TO THE BASIN IN EACH BATHROOM, PER E3801.6.
BATHROOM OUTLETS SHALL BE ON A SEPARATE 20 AMP CIRCUIT WITH NO OTHER OUTLETS, PER E33603.4.--------------INDICATE RECEPT AT LAV. IS ON A DEDICATED 20AMP CIRCUIT


IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
TERRY STEVENS @ 791-5550 EXT. 1112

Final Status

Task End Date Reviewer's Name Type of Review Description
12/31/2002 TAMI ACHONG OUT TO CUSTOMER Completed