Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T02CM05501
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/02/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Based on the provided calculations, the 3/4" water supply to the 9 single units is too small. Revise the pipe sizes. 2. The rim elevation of the upstream manhole is higher than the finished floor elevation; provide backwater valves. Reference Section 710.1, UPC 1994. |
| 06/02/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 06/08/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T02CM05501 DENIED 6/2/04 1. Panel O feeder has a #8 GND, ahead of a 200A CB, is undersized per NEC Table 250-122. 2. Panel 9 feeder has a #8 GND, ahead of a 200A CB, is undersized per NEC Table 250-122. 3. Panel 10 feeder has a #8 GND, ahead of a 200A CB, is undersized per NEC Table 250-122. 4. Please double-check all panels in this installation. |
| 06/11/2004 | CAGUILA1 | ZONING | REVIEW | Needs Review |