Permit Number - T02CM05501
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/02/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Based on the provided calculations, the 3/4" water supply to the 9 single units is too small. Revise the pipe sizes.
2. The rim elevation of the upstream manhole is higher than the finished floor elevation; provide backwater valves. Reference Section 710.1, UPC 1994.
06/02/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
06/08/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T02CM05501 DENIED 6/2/04

1. Panel O feeder has a #8 GND, ahead of a 200A CB, is undersized per NEC Table 250-122.
2. Panel 9 feeder has a #8 GND, ahead of a 200A CB, is undersized per NEC Table 250-122.
3. Panel 10 feeder has a #8 GND, ahead of a 200A CB, is undersized per NEC Table 250-122.
4. Please double-check all panels in this installation.
06/11/2004 CAGUILA1 ZONING REVIEW Needs Review