Review Details: COMMERCIAL NEW

Permit Number - T02CM05501
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/08/2003 JIM EGAN FIRE REVIEW Approved
01/15/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT LBUCZYN1@CI.TUCSON.AZ.US
IF YOU CARE TO DISCUSS.

Sheet E-3
1. Branch circuits for the INSTA HOT units are called out as single phase on Sheet MP 2 but are on 2-pole breakers. Circuiting implies two hots, that is 240V. Please correct/clarify.
2. This is not an electrical code issue, but Sheet MP 2 calls out for two different evaporative coolers, EC-1 and EC-2. Same electrical parameters, but one is 1800 CFM and the other is 3280. This may need clarification.

Sheet E-4
1. On Panel 8, the feeder load calculation, according to the figures shown, totals 149.6A on a 100A panel. This contradicts the 64.7A on the most heavily loaded phase. My calculations total 13726 VA for the panel, for an average 57.2A. Please check, clarify/correct as necessary. Circuit 2, which powers 8 receptacles, should have 1440, not 1260 VA.

Sheet E-5
1. Suggest that Keynote B applies to panel on Keynote 6, which refers to Panel 7, rated at 200A. Using the #2 to feed the only 200A panel, I suspect, was not the intent.
2. Load calculation for Service #1. My check for total comes to 63,611 VA, not 59,311. This would bring the total to 265.0 A as opposed to 247.1. Not a code issue, but it would be more accurate.
01/27/2003 MARTIN HAEBERLE PLUMBING-COMMERCIAL REVIEW Denied 1. Provide complete plumbing plan, including waste and vent isometrics.
2. Provide sizing calculations for domestic water.
3. Existing waste drainpipe in Room 114 reduces from 4" to 2". Please verify correct size.
4. Provide upstream and downstream elevation comparisons with lowest fixture drain to verify need for a backwater valve. Reference section 710 UPC/State code.
5. Provide roof drainage plans.
6. Include in water fixture schedule backflow prevention devices to be used and type.
01/27/2003 MARTIN HAEBERLE MECHANICAL-COMMERCIAL REVIEW Denied Ceiling height too low (7'-0") to accommodate drop box for evaporative coolers.
01/27/2003 RSHERRY1 WATER REVIEW Approved
01/31/2003 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
02/27/2003 GERRY KOZIOL WWM REVIEW Needs Review Plans pulled by client.
02/27/2003 ASHOFFS1 FLOODPLAIN REVIEW Needs Review
12/18/2002 DAVID RIVERA ZONING REVIEW Denied Zoning will approve the building plans after approval by the commercial reviewers and after approval of the site plan.