Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T02CM05474
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/27/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Passed | |
| 02/28/2003 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Denied | City of Tucson, Development Services BUILDING AND STRUCTURAL COMMENTS 1) a) Povide a complete lateral analysis for the building being enclosed. b) If the existing structure is resisting the lateral shear forces, then show how the forces are being distributed to the existing walls. c) Show the roof diaphragm connections(nails,screws,welding)used to transfer the shear loads to the walls and down to the foundation. 2) Provide the engineering design for the beam supporting the roll-up door. Specify the size and show a connection detail of the beam to the door and to the structure. 3) Resubmit plans for review. 3/3/03 1) The special inspector shown on the special certificate is not approved as a special inspector. 2) Specify the structural member at top where the column connects to the roof. Specify type of connection, bolted or welded? Is this connection ediquate for the additioal load? Varify! 3) Show how the supports of the roll-up door are connected to the frame, welded or bolted? Show a detail. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/10/2003 | LISA LESNY | OUT TO CUSTOMER | Completed |