Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T02CM05474
Parcel: 129150020

Address:
1702 S EUCLID AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T02CM05474
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/27/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Passed
02/28/2003 RAUL PALMA BUILDING-COMMERCIAL REVIEW Denied City of Tucson, Development Services
BUILDING AND STRUCTURAL COMMENTS

1)
a) Povide a complete lateral analysis for the building being enclosed.
b) If the existing structure is resisting the lateral shear forces, then show
how the forces are being distributed to the existing walls.
c) Show the roof diaphragm connections(nails,screws,welding)used to
transfer the shear loads to the walls and down to the foundation.
2) Provide the engineering design for the beam supporting the roll-up door.
Specify the size and show a connection detail of the beam to the door and to the
structure.
3) Resubmit plans for review.

3/3/03

1) The special inspector shown on the special certificate is not approved as a special
inspector.
2) Specify the structural member at top where the column connects to the roof. Specify
type of connection, bolted or welded? Is this connection ediquate for the additioal load?
Varify!
3) Show how the supports of the roll-up door are connected to the frame, welded or bolted?
Show a detail.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/10/2003 LISA LESNY OUT TO CUSTOMER Completed