Permit Number: T02CM05474
Parcel: 129150020

Address:
1702 S EUCLID AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T02CM05474
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/12/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied 1. Clarify whether GDOs are to be fed on their own dedicated circuits. GDO specifications on Note 7 indicate a dedicated circuit, but Plan View indicates otherwise.
2. GDOs fed from Panel L are being fed at the wrong voltage.
3. Show load calculation on panel which feeds the 3 GDOs. Add new loads to existing to demonstrate that this panel is not overloaded.
4. Justify 5.4 amps for GDO current. Per NEC Table 430-148 1/2 HP 115V single phase motor draws 9.8 amps FLC.

Call at 791 5550 x1106 if you have any questions.
02/12/2003 JIM EGAN FIRE REVIEW Approved
02/27/2003 MVALDEZ1 BUILDING-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
02/27/2003 MONICA VALDEZ OUT TO CUSTOMER Completed