02/12/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied 1. Clarify whether GDOs are to be fed on their own dedicated circuits. GDO specifications on Note 7 indicate a dedicated circuit, but Plan View indicates otherwise.
2. GDOs fed from Panel L are being fed at the wrong voltage.
3. Show load calculation on panel which feeds the 3 GDOs. Add new loads to existing to demonstrate that this panel is not overloaded.
4. Justify 5.4 amps for GDO current. Per NEC Table 430-148 1/2 HP 115V single phase motor draws 9.8 amps FLC.

Call at 791 5550 x1106 if you have any questions.