| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/12/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1. Clarify whether GDOs are to be fed on their own dedicated circuits. GDO specifications on Note 7 indicate a dedicated circuit, but Plan View indicates otherwise. 2. GDOs fed from Panel L are being fed at the wrong voltage. 3. Show load calculation on panel which feeds the 3 GDOs. Add new loads to existing to demonstrate that this panel is not overloaded. 4. Justify 5.4 amps for GDO current. Per NEC Table 430-148 1/2 HP 115V single phase motor draws 9.8 amps FLC. Call at 791 5550 x1106 if you have any questions. |
| 02/12/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
| 02/27/2003 | MVALDEZ1 | BUILDING-COMMERCIAL | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/27/2003 | MONICA VALDEZ | OUT TO CUSTOMER | Completed |