Permit Number: T02CM05474
Parcel: 129150020

Address:
1702 S EUCLID AV

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T02CM05474
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/09/2003 JIM EGAN FIRE REVIEW Denied 1. Provide information on commodities stored to verfiy S-2 occupancy classification.
2. provide fire sprinkler system design criteria on plan.
a. Design standard to be used.
b. Hazard classification.
c. Minimum design density and area of application.
d. Water supply information:
Static PSI__ Residual PSI__ Flow__GPM
01/13/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT LBUCZYN1@CI.TUCSON.AZ.US
IF YOU CARE TO DISCUSS.

1. Provide specifications for the door operator motors. Current, voltage, horsepower, phase, overload protection.
2. Specify circuit breaker size at panel feeding door opener motors.
3. Specify conductor size and insulation type.
4. Indicate presence and location for switch/disconnect for door operator motors.
5. Specify overload protection for door opener motors, unless provided with the equipment.
6. Provide load calculation accounting for new load on existing panel.
01/30/2003 RAUL PALMA BUILDING-COMMERCIAL REVIEW Denied City of Tucson, Development Services
BUILDING AND STRUCTURAL COMMENTS

1)
a) Povide a complete lateral analysis for the building being enclosed.
b) If the existing structure is resisting the lateral shear forces, then show
how the forces are being distributed to the existing walls.
c) Show the roof diaphragm connections(nails,screws,welding)used to
transfer the shear loads to the walls and down to the foundation.
2) Provide the engineering design for the beam supporting the roll-up door.
Specify the size and show a connection detail of the beam to the door and to the
structure.
3) Resubmit plans for review.
01/31/2003 GERRY KOZIOL WWM REVIEW Approved
02/03/2003 MARTIN HAEBERLE MECHANICAL-COMMERCIAL REVIEW Passed
02/03/2003 MARTIN HAEBERLE PLUMBING-COMMERCIAL REVIEW Passed
02/03/2003 MARTIN HAEBERLE WATER REVIEW Passed
02/06/2003 PATRICIA GEHLEN ZONING REVIEW Approved
02/07/2003 JAMES TATE FLOODPLAIN REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/10/2003 CINDY AGUILAR OUT TO CUSTOMER Completed