Permit Number: T02CM05432
Parcel: 13217141B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T02CM05432
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/22/2002 JIM EGAN FIRE REVIEW Approved
11/22/2002 JAMES TATE FLOODPLAIN REVIEW Approved
11/22/2002 DAVID RIVERA ZONING REVIEW Approved
12/03/2002 MARTIN HAEBERLE PLUMBING-COMMERCIAL REVIEW Passed
12/03/2002 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Denied 1. The proposed occupant load does not reflect the minimum number of plumbing fixtures as required by Table 2902.1 of the IBC. Revise plans to meet the minimum plumbing fixtures per Table 2902.1 of the IBC.
2. Proposed storage room is required to have a 1-hour separation as per Table 302.1.1 of the IBC. Revise plans to reflect the required separation.
3. Storage room is to have minimum protection of openings for a 1-hour fire barrier. Revise plans to indicate required protection of the door assembly and duct penetration. Reference Table 714.2 IBC
4. Provide bracing for interior partition walls. Reference section 1604.3.1 IBC
5. Provide hardware schedule for exit doors and fire door.
6. Exit door requires 12" side approach clearance if door and closer used. Please clarify. Reference figure 404.2.4.1 ANSI A117.1
7. Illuminated signage is not provided at all required exits. Reference section 1003.2.10 IBC. Revise plans.
12/03/2002 MSTPAUL1 WWM REVIEW Passed
12/03/2002 MHAEBER1 WATER REVIEW Approved
12/03/2002 MARTIN HAEBERLE MECHANICAL-COMMERCIAL REVIEW Approved
12/06/2002 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Denied 1.Font size is too small at panel schedules. 2.Indicate panel designation oncircuiting. 3.Add exit lights per structural reviewers comments and revise calculations to reflect added load. 4.Correct panel schedules (cir. 13 is not described @ panel "AB", and@ panel "A" it's described as evap. cooler? 5.Indicate the allowed wirig method (conduit/MC cable etc.).

Final Status

Task End Date Reviewer's Name Type of Review Description
12/06/2002 CINDY AGUILAR OUT TO CUSTOMER Completed