Permit Review Detail
Review Status: Completed
Review Details: REVISION
Permit Number - T02CM05372
Review Name: REVISION
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/16/2003 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Denied | City of Tucson, Development Services BUILDING AND STRUCTURAL COMMENTS 1. Provide proof of compliance with section 2407. ( Glazing in railing-in-fill panels shall conform to ANSI Z 97.1 listed in chapter 35 of the IBC 2000). 2. The fax sheet no. P003, at bottom of sheet, specifies that the tests were performed under a diff- erent code and the safety factor was ignored, therefore another test under the current code would 3 Show a detail connection of escalator to structure and cross referance. 4 Specify the number of bolts and size, or the size of weld and length as per engineering design. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/27/2003 | MONICA VALDEZ | OUT TO CUSTOMER | Completed |
| 05/16/2003 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |